5.3.4.1 General
Guide lines and installation instructions
The flue gas discharge and the air supply systems must be installed by a recognised installer in
accordance with the applicable national regulations.
The total resistance of the air supply and the flue should not result in a pressure drop exceeding
1.8 mbar (types 73 and 90) or 1.0 mbar (types 115 to 287).
Extreme care must be taken to limit the draught of the attached flue and air supply system to below
15Pa in all firing conditions.
5.3.4.2 Air supply pipe
The air supply pipe may be single-walled and constructed of:
- plastic
- thin-walled aluminium
- flexible aluminium (take account of the resistance)
- stainless steel.
- it is essential that the combustion air intake grille does not allow direct wind attack that could effect
the combustion process of the unit.
Fig. 5 horizontal air supply
Type
Air supply diameter D1 (mm)
73 100
90
100
115
125
146
125
192
150
241
180
287 180