background image

© MHG Heating Ltd 

 

11  

MHG Heating Ltd, Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey, KT20 5LR 

Phone 0845 6448802 Telephone. 0845 6448803 Fax. Email 

[email protected]

 Website www.mhgheating.co.uk 

010313 

 Draft 

 

 

 

Worked Example 

The example below is for a G

1

/

temperature relief valve with a discharge pipe (D2) having 4 no. elbows and length of 7m from the tundish to the point of discharge. 

 

From Table 1 

Maximum resistance allowed for a straight length of 22mm copper discharge pipe (D2) from a G

1

/

temperature relief valve is: 9.0m. Subtract the resistance for 4 No. 22mm elbows at 

0.8m each = 3.2m 
 
Therefore the maximum permitted length equates to: 5.8m 
 
5.8m is less than the actual length of 7m therefore calculate the next largest size. 
 
Maximum resistance allowed for a straight length of 28mm pipe (D2) from G1/2 temperature relief valve equates to: 18m. 
 
Subtract the resistance for 4 No. 28mm elbows at 1.0m each = 4m. 
 
Therefore the maximum permitted length equates to 14m. 
 
As the actual length is 7m, a 28mm (D2) copper pipe will be satisfactory. 
 

NOTES ON WATER QUALITY AND SCALING 
 

Water hardness can vary considerably around the country. If furring of kettles normally occurs in the area, then the unit should be fed with 
conditioned water only. This can be provided by a water softener with a high capacity flow rate, or a suitable water conditioner (not supplied). 
It is recommended that the temperature controls are set below 65

0

C to prevent lime scale build up. 

The performance of all water storage appliances and their associated components may deteriorate if you do not protect adequately against 
hard water scaling. If more than 150ppm salts are present in local water samples, an effective conditioner should always be used. 
 

Maintenance 
 

The following checks should be conducted annually: 
 
Check the operation of the T & P valve and Expansion valve by rotating the heads of the valves in turn until water is discharged. The 
discharge should stop immediately when the valve head is released. Should this not be the case the valve should be replaced. Check that the 
discharged water flows freely to waste and that there is no blockage. 
 
Remove and clean the filter in the Pressure Reducing Valve. 
 
Check that the expansion vessel charge pressure is set at 0.2 bar below the incoming pressure. If water is being discharged from the expansion 
valve it may be indicative of pressure loss within the expansion vessel itself. To check the pressure, isolate the unit from the cold supply and 
release any pressure by opening a hot tap until water stops flowing. Then use a tyre pressure gauge to verify the charge pressure. If the unit is 
more than 5 years old when this problem is experienced it may be advisable to replace the pressure vessel. If however, the pressure in the 
expansion vessel is 0.2 bar below incoming pressure the discharge may be being caused by back pressure or cross-over between the cold and 
hot water supplies - see below. 
 
To replace the pressure vessel, unscrew from threaded connection. The new pressure vessel should be adjusted to 0.2 bar below incoming 
pressure and then fitted to the cylinder, ensuring that the threads are sealed appropriately. 

 

Содержание Unvented Calorifer Range

Страница 1: ...t 4 Epsom Downs Metro Centre Waterfield Tadworth Surrey KT20 5LR Phone 0845 6448802 Telephone 0845 6448803 Fax Email info mhgheating co uk Website www mhgheating co uk 010313 Draft Unvented Calorifer Range Installation and Operating Manual ...

Страница 2: ...3 Connections Single Coil Indirect Unit 4 Twin Coil Indirect Unit 4 Unvented Items Supplied 5 Dimension Single Coil Indirect 90 500 5 Single Coil Indirect 90 500 High Recovery 5 Twin Coil Indirect 90 500 6 Single Coil Indirect 600 1000 6 Direct 90 500 6 Installation Procedure 7 Performance Data 7 Commissioning Operating 9 Building Regulations 10 Discharge Pipes 10 Notes on Water Quality and Scalin...

Страница 3: ...anty Do not remove or adjust any component part of this unvented water heater Contact the installer If this unvented water heater develops a fault such as a flow of hot water from the discharge pipe switch the heater off and contact the installer WARNING TO INSTALLER This installation is subject to building regulation approval notify Local Authority of intention to install Use only manufacturer s ...

Страница 4: ...its 5 Thermostat Pocket 22mm Indirect unit Only 22mm Indirect unit Only 22mm Indirect unit Only 6 Temperature and Pressure Relief Valve Fitted Fitted Fitted Twin Coil Indirect Unit Description Connection Size 90 300L Connection Size 400 500L Connection Size 600 1000L J Cold Fill 22mm 28mm 28mm D Boiler Primary Flow and Return 22mm 28mm 28mm B Hot Water 22mm 28mm 28mm F Immersion Element 3kW 1 Phas...

Страница 5: ...Valve Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Cylinder Thermostat Indirect Only Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Energy Cut Off valve 2 Port Spring Return Zone Valve Indirect Only Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Tundish Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Expansion Vessel 8L Yes Expansion Vessel 12L Yes Yes Expansio...

Страница 6: ...psom Downs Metro Centre Waterfield Tadworth Surrey KT20 5LR Phone 0845 6448802 Telephone 0845 6448803 Fax Email info mhgheating co uk Website www mhgheating co uk 010313 Draft Twin Coil Indirect 90 500 Single Coil Indirect 600 1000 Direct 90 500 ...

Страница 7: ... draw off mins High Recovery Heat Up Time to 55C mins High Recovery Reheat time to 60C after 70 draw off mins 90 125 750 510 26 18 13 9 125 165 935 510 36 25 19 13 150 195 1060 510 37 26 19 13 170 220 1200 510 36 25 19 13 200 250 1120 554 33 24 17 12 250 310 1330 554 35 25 18 13 300 360 1650 554 40 29 20 15 400 480 1590 660 46 34 23 18 500 580 1835 660 52 39 25 20 600 715 1435 822 69 34 51 29 700 ...

Страница 8: ... at least 300mm of straight metal pipe below it before any elbow or bend The pipework below the tundish should be fitted in accordance with the current edition of the Building Regulations The discharge from the expansion valve on the Inlet Control Group must be connected into the discharge pipe work We recommend a double check valve should be fitted to the hot water draw off to prevent any back pr...

Страница 9: ...er control setting is set between 55 C and 65 C for economical operation The upper limit thermostat is set to 80oC and must not be tampered with Commissioning Operating Ensure all connections are fully tightened Open all of the hot taps supplied by the cylinder and slowly fill the unit by opening the service valve Continue to fill the unit until water runs continuously from all of the open taps Op...

Страница 10: ...b Have a vertical section of pipe at least 300mm long below the tundish before any elbows or bends in the pipework c Be installed with a continuous fall d Have discharges visible at both the tundish and the final point of discharge but where this is not possible or is practically difficult there should be clear visibility at one or other of these locations Examples of acceptable discharge arrangem...

Страница 11: ...e of all water storage appliances and their associated components may deteriorate if you do not protect adequately against hard water scaling If more than 150ppm salts are present in local water samples an effective conditioner should always be used Maintenance The following checks should be conducted annually Check the operation of the T P valve and Expansion valve by rotating the heads of the va...

Страница 12: ... and maintained in accordance with the installation instructions The product has not been subjected to damage caused by frost or other external influence The Guarantee Card supplied with the product has been completed and returned within 90 days of installation The immersion heater water control valves cylinder thermostat expansion vessel and energy cut out valves are guaranteed for two years from...

Страница 13: ... 13 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre Waterfield Tadworth Surrey KT20 5LR Phone 0845 6448802 Telephone 0845 6448803 Fax Email info mhgheating co uk Website www mhgheating co uk 010313 Draft Fault Finding ...

Страница 14: ...313 Draft Installed by Name Address Tel No Completion Date Unit Type Indirect Direct APPLIANCE SERIAL NO Capacity Weight In Service Record Activity Date Parts Replaced Installer Names and Unvented Registration number Installed Commissioned 1st Service 2nd Service 3rd Service 4th Service 5th Service 6th Service 7th Service 8th Service 9th Service 10th Service 11th Service 12th Service 13th Service ...

Страница 15: ... Ltd 15 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre Waterfield Tadworth Surrey KT20 5LR Phone 0845 6448802 Telephone 0845 6448803 Fax Email info mhgheating co uk Website www mhgheating co uk 010313 Draft Notes ...

Отзывы: