© MHG Heating Ltd
Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey, KT20 5LR
Telephone 08456 448802 Fax 08456 448803 Email
Web
www.mhgheating.co.uk
010709 Draft
4
Technical Data
Gas Condensing Boiler
Description
Unit
Product Number
CE-0063AR3527
Category
II2ELL3P
Weight
Kg
64
Dimensions
mm
1070 x 870 x 450
Primary Water Content
L
1.4
Heating Flow & Return
mm
22
DHW Inlet & Outlet
mm
15
Gas Supply Inlet
mm
15
Flue Gas/Combustion Air
mm
80/125
Nominal Input
kW
7.2 – 27.3
Nominal Output 80/60
°C
kW
7.0 – 26.2
Nominal Output 50/30
°C
kW
7.7 – 26.8
Nominal Efficiency 80/60
°C
%
97.2 – 96.0
Nominal Efficiency 50/30
°C
%
98.2 – 106.9
Nominal Efficiency 40/30
°C
%
101.0 – 108.5
Maximum Flow Temperature
°C
90
Nominal Mass Flow Rate @20
Δ
T
L/h
1160
Maximum Operating Pressure
bar
3
Maximum Inlet Gas pressure
mbar
50
Minimum Inlet Gas Pressure
mbar (N/
L)
18/35
Nominal Power Input
V / Htz
230/50
Installation Categories
B
23
, B
33
, C
13X
, C
33X
, C
43X
, C
53X
, C
63X
, C
83X
Residual Flue Gas Pressure
Pa
90
Flue Gas Temperature @ 80/60
°C
°C
94