background image

4—6

Содержание Esprit 3

Страница 1: ...Made in USA Made in USA Slim Line Rack UPS User s Manual Models 3 4 www mgeups com...

Страница 2: ...UPS SYSTEMS 1660 Scenic Avenue Costa Mesa CA 92626 714 557 1636 www mgeups com Revision History Esprit Rack UPS User s Manual 86 153301 03 Copyright 2000 MGE UPS Systems All rights reserved Printed in...

Страница 3: ...cuit protection Do not place Esprit near water or in an environment of excessive humidity Do not allow liquids or foreign objects to get inside Esprit Do not block air vents in front on top or on bott...

Страница 4: ...ear rubber gloves boots and safety glasses Determine if the battery is inadvertently grounded Please dispose of the packaging in accordance with applicable laws Federal Communication Commission FCC St...

Страница 5: ...packing the UPS 3 1 3C Placement of the UPS 3 1 Rack Mounting 3 1 3D Optional Accessories 3 1 3E Connecting the Optional Extended Battery 3 2 3F Disconnecting the UPS Battery to Take Out of Service 3...

Страница 6: ...Fine MGE Products inside back cover Figures 2a Rear View of Models 3 and 4 With Rack Kit and Extended Batteries 2 2 2b Optional Rack Mounting Kit 2 2 2c Typical Front Views of Models 3 4 Extended Batt...

Страница 7: ...ing are also provided in this mode The UPS instantly transfers the load to the battery when a power failure occurs If the power returns before the battery is exhausted the operation returns to normal...

Страница 8: ...1 2...

Страница 9: ...and fastest Other communications optional communications communications possible Network based power Multiple server shutdown and management software supervision Web management New standard for web Ea...

Страница 10: ...of electric shock even when input power is removed Do not remove cover No user serviceable parts inside Refer to qualified service personnel In Ue Eing Entrada Do not disconnect under load Vac In Ue E...

Страница 11: ...it upright and then remove the packing material Save packaging for future shipment of UPS to MGE for recycling 3C Placement of the UPS Choose a location out of direct sunlight with adequate ventilatio...

Страница 12: ...will need the RS232 serial port or a USB Universal Serial Bus port The connection will be made between your computer s serial or USB port and the serial or USB port on the rear of the UPS module as sh...

Страница 13: ...ectrician Table 3a UPS Wiring Information Figure 3c AC Line Cord of the Extended Battery Model Plug Amp rating 3 L5 30 30 4 5 50 50 3I Connecting the Loads Utilize the receptacles on the rear of the U...

Страница 14: ...o the UPS 3J Solution Pac Software Solution Pac software allows you to interface your computer with the UPS The software is loaded on your computer and through the communication port can access and re...

Страница 15: ...iagnostics as well as check utility power After depressing the green On button and starting your UPS for the first time you will hear an audible beep confirming the button has been depressed and your...

Страница 16: ...Utility power is present and within specification limits On Inverter On Mode Utility power is available but is outside specification limits On Flashes Battery Low A low battery warning will sound Ack...

Страница 17: ...an the UPS itself 4 Output The UPS is capable of The UPS is heavily The UPS is slightly over loaded Overload supporting the load overloaded Automatic The UPS will continue to sup yellow connected to i...

Страница 18: ...if it is active If a new alarm fault is detected after a silence operation the beeper will be re activated to issue the new alert This button sequence can be thought of as an alarm fault acknowledge f...

Страница 19: ...lem is corrected Fault LED and Charge Charger Problem Warning The battery system may not be LED flashes until alarm long short long short beep plugged into an AC source or is acknowledged or problem t...

Страница 20: ...4 6...

Страница 21: ...mode voltage 120 VAC or 5 120 VAC mode Battery life expectancy 3 5 years Output frequency regulation Nominal or 0 5 HZ On battery Battery mode output protection Electronic current limit Self protected...

Страница 22: ...X 19 Weight 65 70 lbs total MTBF 200K hours Sizing Guide and Battery Runtimes In minutes 0 62 PF Unix Server 1 2 3 4 server servers servers servers PC Server 1 2 3 4 5 6 7 8 server servers servers ser...

Страница 23: ...The AC PRESENT indicator blinks slowly during the time that the Esprit is in configuration mode To exit configuration mode press and hold both top and bottom buttons again The AC PRESENT indicator wi...

Страница 24: ...he options that can be changed by the user in configuration mode and shows which front panel indicators will be on for each option Option Indicators Number Fault Batt Fail Charge Overload Option affec...

Страница 25: ...4 SlimLine Internal only 1 2 3 4 5 6 7 Indicators Option On illuminated Option Off dark Options 3 4 Operating voltage selection These two options select the nominal operating voltage of the UPS as sh...

Страница 26: ...attery contact without actually running the Esprit battery down To clear the User Test Fault set this option to OFF or follow the Alarm Clear procedure Press and hold the top button Option 8 Limit run...

Страница 27: ...default ON setting the Esprit will analyze the input power when it is turned on and configure itself to operate at the proper frequency 50 or 60 Hz If utility power is not present when the Esprit is...

Страница 28: ...he POIT is enabled the UPS will power up the load from utility power then briefly switch to battery power approximately 5 7 seconds after it is powered up The UPS runs on battery for only 3 5 seconds...

Страница 29: ...utility power due to disconnection of the safety ground 2 Allow the UPS to run on battery power for 1 minute Monitor the UPS for any fault LEDs and if none are observed return power to UPS and log res...

Страница 30: ...all 1 714 557 1636 M F 6 00 A M to 5 00 P M PST Ask for a return goods authorization for free UPS or battery recycling MGE does not cover return freight charges for recycling and will not accept items...

Страница 31: ...l socket repair as remains on even though specification required line voltage is present UPS beeps occasionally UPS is on battery None UPS is protecting your system UPS does not provide Battery capaci...

Страница 32: ...Notes 8 2...

Страница 33: ...0 2200 VA 780 2200 VA EX UPS EX Rack UPS 700 3000 VA 700 3000 VA Call MGE for many more power solutions 714 557 1636 or 800 523 0142 US MGE GREEN SWEEP Call MGE to return your UPS for free recycling t...

Страница 34: ...MGE UPS SYSTEMS USA headquarters 1660 Scenic Avenue Costa Mesa CA 92626 tel 800 523 0142 714 557 1636 fax 714 557 9788 www mgeups com...

Отзывы: