51033777EN/AB

2.5 Connecting the batteries to the connection box

Use a 3-conductor cable (shielded, max.
length 6 m, 3 x 10 mm

2

 conductors) to be

passed through the shielded cable gland.

Use a 50 A circuit breaker
(curve B) for protection.

Note: 

the cable and circuit breaker are not

supplied with the product.

1. Prepare the cable.

2. Unscrew the cover and dismantle the
metal cable gland of the connection box.

3. Mount the cable gland on the shielded
cable.

4. Connect the 3 conductors to the terminal
block and refit the connection box cover.

5. Connect the other end of the cable to the
circuit breaker.

2.6 Connecting the Comet EX

treme

 CLA modules to the power source

Use flexible cables (3 x 2.5 mm

2

 conductors)

to be passed through the plastic cable
gland.

Always connect the earth wire
first. Use a 10 A circuit breaker
(curve C) for protection.

Note: 

the cable and circuit breaker are not

supplied with the product.

1. Prepare the cable.

2. Unscrew the plate with the plastic cable
gland.

3. Connect the 3 conductors and remount
the plate.

2. Installation

1

50A

t

In

B

10

90

10

50A

12V-65Ah

5

5

4

2

2

3

10

50

2

L +

RESEA

U/MAINS/NETZ

N

3

1

Содержание Comet EXtreme CLA 12 kVA

Страница 1: ...51033777EN AB Page 1 www mgeups com MGE UPS SYSTEMS Comet EXtreme CLA 12 kVA Installation manual N O T H I N G W I L L S T O P Y O U N O W...

Страница 2: ...Page 2 51033777EN AB...

Страница 3: ...1 Unpacking Comet EXtreme CLA module connection cable documentation 1 2 connection box installation manual telescopic rails and 19 rack mounting hardware 4 5 Comet EXtreme CLA 12 kVA Tower model Rack...

Страница 4: ...n the rack The rails and the screws required to mount them are included in the box To mount the connection box in a rack use the mounting brackets and screws packed with the connection box 2 1 Mountin...

Страница 5: ...The connection of each module to the electrical supply must be protected by an easily accessible circuit breaker not supplied A module can be isolated from the electrical supply by opening this circui...

Страница 6: ...ct the 3 conductors to the terminal block and refit the connection box cover 5 Connect the other end of the cable to the circuit breaker 2 6 Connecting the Comet EXtreme CLA modules to the power sourc...

Страница 7: ...itch the battery circuit breaker to ON position 2 Connect a PC to the UPS using an RS232 cable 3 Run the UPS Driver software installed on a diskette Go to the battery menu and select the battery backu...

Страница 8: ...r CLA 8 hr CLA 2 hrs 30 min 5 hrs 40 min 9 hrs 3 hrs 30 min 7 hrs 30 min 13 hrs 40 min 5 hrs 20 min 13 hrs 40 min 21 hrs Recharge time to 90 full backup time Comet EXtreme CLA 12kVA 2 hr CLA 9 hrs 4 h...

Страница 9: ...5103377700 AB...

Страница 10: ...5103377700 AB MGE UPS SYSTEMS 140 Avenue Jean Kuntzmann ZIRST Montbonnot St Martin 38334 Saint Ismier Cedex France www mgeups com Nothing will stop you now 5103377700 AB...

Отзывы: