3.4.4
Voltage Measurements Screen
The
Voltage Measurements
screen displays the voltage
presently on any one of the input phases (AC N and AC BP)
and each phase of the load, as well as the differential
voltage as measured between any two phases of the inputs
and the load. See Figure 3-9.
3.4.5
Frequency Measurements Screen
The
Frequency Measurements
screen displays the
frequency presently on any one of the input lines (AC N and
AC BP) and the load. See Figure 3-10.
3.4.6
Ratios Screen
The
Ratios
screen displays the crest factor for each phase,
the present percentage of load for each phase and for the
total unit. Additionally, the load in KVA/KW is provided. See
Figure 3-11.
Galaxy 4000
Display Panel
3 — 6
86-173010-00 A00
Figure 3-9: Voltage Measurements screen.
Figure 3-10: Frequency Measurements screen.
Figure 3-11: Ratios screen.
Ratios
Crest Factor %Load
Ph1 1.5 13 %
Ph2 1.5 13 %
Ph3 1.5 13 %
Load kW/kVA 0.8
kW percent load 12 %
Frequency measurements
Load AC N AC BP
60.0 Hz 59.9 Hz 59.9 Hz
Voltage measurements
Load AC N AC BP
V1 120 V 121 V 120 V
V2 120 V 121 V 120 V
V3 121 V 121 V 120 V
U12 207 V 209 V 209 V
U23 207 V 209 V 209 V
U31 207 V 209 V 209 V
Содержание 40-75KVA
Страница 2: ......
Страница 6: ...Galaxy 4000 iv 86 173010 00 A00...
Страница 12: ...Galaxy 4000 VI 86 173010 00 A00...
Страница 26: ...This page left blank intentionally Galaxy 4000 2 8 86 173010 00 A00...
Страница 36: ...This page left blank intentionally Galaxy 4000 Display Panel 3 10 86 173010 00 A00...
Страница 42: ...This page left blank intentionally Galaxy 4000 5 2 86 173010 00 A00...
Страница 50: ...Galaxy 4000 G 4 86 173010 00 A00 This page left blank intentionally...
Страница 52: ......
Страница 53: ......
Страница 54: ......
Страница 55: ......