7. Mounting

Power down the equipment

Mount the module on standard rail (TH35 per IEC 60715 in  

junction boxes and/or on distribution panels).

Installation

Electric installation and device termination shall be done by 

qualified persons only, by respecting all applicable  

specifications and regulations.

Plug in the terminal block for bus connection

The module can be aligned without interspace. Use the jumper 

plug to connect bus and supply voltage when the modules are 

mounted in series.

The maximum quantity of modules connected in line is limi-

ted to 15 or to a maximum power consumption of 2 Amps 

(AC or DC) per connection to the power supply. For any 

similar block of additional modules a separate connection 

to the power supply is mandatory.

Connect the cable for bus supply

Mounting in series

5 mm

1

2

3

4

5

6

8.  Software Description

Node Object

Node Object

nvoStatus  

SNVT_obj_status

nviRequest  

SNVT_obj_request

nvoFileDirectory 

SNVT_address

SCPTmaxSendTime

The Node Object monitors and controls the functions of the  

different objects in the device. It supports the basic functions 

Object-Status and Object-Request required by LonMark.
nviRequest 

SNVT_obj_request

nvoStatus 

SNVT_obj_status

nvoFileDirectory 

SNVT_address

SCPTmaxSendTime  SNVT_time_sec

All output variables described below will be issued at the latest 

at the end of the preset period even without status change.
Time settings: 

0 timer function off-state 

   

6553 s (factory setting 60 s)

DO_1 - 4 Objects 

DO_1 - 4 Objects

nvoFeedback_1..4

SNVT_switch

nviValue_1..4 

SNVT_switch

The respective relay is switched on through the nviValue_1..4 

variable with a value having a value portion above 0 and 

a state portion of 1, in all other cases the relay is switched off. 

nvoFeedback_1..4 

SNVT_switch

Transmits the feedback value of the object.
Automatic mode ON: 

100,0 1 

Automatic mode OFF: 

0,0 0 

Manual mode ON: 

100,0 -1 

Manual mode OFF: 

0,0 -1

nvoManualFb_1..4   SNVT_switch

Transmits the manual control feedback.
Manual switch 

  on automatic 

100,0 1 

  on “0” or “1” 

0,0 0

SCPTInvrtOut 

SNVT_lev_disc

Inverting the relay switching states when actuated by 

nviValue_1..4.
Applicable values: 

ST_ON contact open; 

nviValue_1..4 set. 

ST_OFF contact closed; 

nviValue_1..4 set.

nvoManualFb_1..4 

SNVT_switch

nviValue_1..4 

SNVT_switch

SCPTInvrtOut

SCPTdelayTime

Continuation Sotftware Description

SCPTdelayTime 

SNVT_time_sec

Wiper function. When nviValue_1..4 is set and the preset period 

is over the relay changes status. In the manual mode the wiper 

function is off-state.
Applicable values:  

0 wiper function off-state 

   

6553 s (factory setting 0 s)

Содержание Logline LF-DO4

Страница 1: ...chtigung der innerbetrieblichen Vorschriften Kenntnis der Unfallverhütungsvorschriften Kenntnisse über den Einsatz und Gebrauch des Geräts inner halb des Anlagensystems usw METZ CONNECT GmbH Im Tal 2 78176 Blumberg Deutschland Tel 49 7702 533 0 Fax 49 7702 533 433 Montageanleitung siehe www metz connect com 3 Technische Daten LON Schnittstelle Übertragung TP FT 10 free topology Neuron FT5000 Daten...

Страница 2: ...y LonMark nviRequest SNVT_obj_request nvoStatus SNVT_obj_status nvoFileDirectory SNVT_address SCPTmaxSendTime SNVT_time_sec All output variables described below will be issued at the latest at the end of the preset period even without status change Time settings 0 timer function off state 6553 s factory setting 60 s DO_1 4 Objects DO_1 4 Objects nvoFeedback_1 4 SNVT_switch nviValue_1 4 SNVT_switch...

Страница 3: ...l directions Knowledge of safety rules Knowledge about application and use of the device within the equipment system etc 3 Technical Data LON interface Transceiver TP FT 10 free topology Neuron FT5000 Data format standard network variables SNVT Transmission rate 78 kBit s Max length Line topology 2700 m 64 nodes Free topology 500 m 64 nodes Cabling Twisted Pair Application software XIF and NXE fil...

Страница 4: ... Request required by LonMark nviRequest SNVT_obj_request nvoStatus SNVT_obj_status nvoFileDirectory SNVT_address SCPTmaxSendTime SNVT_time_sec All output variables described below will be issued at the latest at the end of the preset period even without status change Time settings 0 timer function off state 6553 s factory setting 60 s DO_1 4 Objects DO_1 4 Objects nvoFeedback_1 4 SNVT_switch nviVa...

Отзывы: