Metso Jamesbury 4000 Series Скачать руководство пользователя страница 3

Jamesbury 3-Piece Ball Valves, Series 4000, Threaded End, Socket Weld, Butt Weld, Rev 2.0, Safety Manual 

3

1.

Introduction

This safety manual provides the functional safety related information required to integrate and use Metso 

Jamesbury Series 4000 3-piece ball valves in safety systems in compliance with the IEC 61508 standard. This 

safety manual shall be used together with the Installation, Maintenance, and Operation manual for Series 4000 

3-piece ball valves.
The Series 4000 3-piece ball valve is a quarter turn valve, which is used in automated on/off and control process 

applications. In on/off service, the valve is either fully closed or fully open. The Series 4000 3-piece ball valves is 

commonly part of an automated on/off (block) valve assembly, which consists of a valve, actuator, accessories, 

and linkage parts. Only the valve component of the automated on/off valve assembly is considered in this 

document. The actuator part of the assembly can be one of several quarter turn pneumatic types such as a rack 

and pinion, piston, etc. Actuators may also be electrically or hydraulically powered.  Accessory parts of the au-

tomated on/off valve assembly may include a partial stroke test device, such as a Neles ValvGuard or solenoid 

valves.  Instruments such as quick exhaust valves, boosters and/or limit switches may be present.
In safety applications, the automated on/off valve assembly is part of safety instrumented function (SIF), The 

SIF purpose is to protect plant, environment and personnel against a hazard. In safety systems, the valve as-

sembly is commonly called a final element subsystem. The primary function of the final element is to either 

isolate (block) the process, or to release or vent (blowdown) energy such as pressure, from the vessel.

2.

Structure of the 3-piece ball valves

2.1 

Components and description of use

See the appropriate IMO (203 or 210) or the documentation available for the valve for a detailed technical 

description.

2.2 

Permitted valve types 

The information in this manual pertaining to functional safety applies to many different valve sizes, end con-

nection types, and variants mentioned in the type coding in the IMO’s. The valve can be used in valve fail-open 

or valve fail-closed actions, depending on actuator installation and selection.

2.3 

Supplementary valve documentation 

1. Installation, Maintenance and Operating Instructions IMO - 203, 210

2. Technical Bulletin B105-1

These are available from a Metso contact, or for download from www.metso.com/valves.
Note that the IMO is not always shipped with the product.

3.

Using the 3-piece ball valve in safety systems

3.1 

Safety function

When de-energised, the complete valve assembly goes to its fail safe position. The safety position of the bare 

shaft valve can correspond to either valve fully closed or fully open. The safety action within the assembly is 

normally initiated by a solenoid valve or intelligent partial stroke device. This releases actuator power, causing 

the actuator to reach its safety position. Hence, the safety function of valve and actuator is a quarter turn (full 

stroke) rotation either to close the fluid flow through the valve or open the fluid flow through the valve. 
The spring in a single acting pneumatic actuator forces the actuator and valve to reach its safety position. The 

secure instrument air (SIA) buffer vessel is commonly used together with a double acting pneumatic actuator 

to provide a safety function. The SIA is not considered in this document.

Содержание Jamesbury 4000 Series

Страница 1: ...10SM 4000 en 5 2017 Jamesbury 3 Piece Ball Valves Series 4000 Threaded End Socket Weld Butt Weld Rev 2 0 Safety Manual ...

Страница 2: ...ems 3 3 1 Safety function 3 3 2 Environmental and application restrictions 4 3 3 Useful lifetime 4 3 4 Connecting the 3 piece ball valve to a safety system 4 3 5 Random hardware integrity 5 3 6 Systematic integrity 5 3 7 Additional information 5 4 Installation 6 5 Operation 6 5 1 Recommended proof test 6 5 2 Recommended partial stroke test 6 5 3 Maintenance 7 6 References 7 Appendix 1 Examples of ...

Страница 3: ...element is to either isolate block the process or to release or vent blowdown energy such as pressure from the vessel 2 Structure of the 3 piece ball valves 2 1 Components and description of use See the appropriate IMO 203 or 210 or the documentation available for the valve for a detailed technical description 2 2 Permitted valve types The information in this manual pertaining to functional safety...

Страница 4: ...1 Partial Stroke test 5 2 Maintenance 5 3 have been considered accordingly The useful lifetime is the time period after burn in and before wear out when the failure rate of a simple item is more or less constant Note that the design life of the valve is higher and should not be con fused with useful lifetime used in these reliability evaluations 3 4 Connecting the 3 piece ball valve to a safety sy...

Страница 5: ...ure Fraction SFF N A Dangerous failures λD failures hour 1 76E 8 Dangerous undetected failures λDU failures hour 1 76E 8 Dangerous detected failures PST λDD failures hour 0 Safe failures λS failures hour 2 99E 8 Diagnostic coverage represents common valve actuator assemblies equipped with an intelligent part stroke device such as the Neles ValvGuard The DC value has been used to calculate λDU and ...

Страница 6: ... visual inspection Check that the SIS valve is in the normal position and verify that all ac cessories are operating according the specification for the SIS valve normal operation Inspect visually that there is no observable deterioration of the SIS valve Record all results and observations into the corresponding database with necessary audit trail information Remove the SIS valve bypassing if use...

Страница 7: ... lifetime and with the severity of service Only authorized Metso replacement parts should be used Soft sealing materials especially are affected by aging and useful lifetime depends strongly on the application Therefore the condition of those components should be checked carefully during proof testing In optimum operating conditions the maintenance interval may be extended up to 10 years The estim...

Страница 8: ...actuator equipped with solenoid valve control for safety action Appendix 2 Equations to calculate PFD for 1oo1 and 1oo1D final elements These equations correspond to IEC 61508 and ISA TR 96 05 01 An average value of probability of failure on demand for 1oo1D architecture with diagnostics is given by the equation PFDAVG DC λD TIPST 2 1 DC λD TIFST 2 λD MTTR where DC is diagnostic coverage fraction ...

Отзывы: