Model PDP Series 200 maxDPU4F Hardware Guide
Metso Automation
•
278705
•
1-4
cables should be laced to the left side of the chassis with at least a 1 inch
bend radius to allow for easy removal of the DPU, while limiting the strain
on the RJ45 connectors.
When using a second DPU for backup, it should be mounted vertically
beneath the primary DPU for ease of connection of the two-foot backup
cable. The cable is to be held in place by tying to the cable hold downs on
the side of the IOP rack.
The DPU is designed to allow installation and removal with the +24 V dc
power supply turned on.
Positioning the DPU When Upgrading
The DPU can be mounted on the right side of a Six Wide maxPAC chassis or
any slot of the Four Wide Model 564 chassis. In either case, remove all
mounting hardware and termination panels that supported the earlier model
DPU. Install a
Chassis 4 Wide maxPAC
adapter (Metso Automation
#047350) in the cleared space using the two mounting holes located in the
back panel metal frame.
If the previous DPU was a DPU4E, the Ethernet cables that were plugged
into the termination panel can be plugged directly into the front panel of the
DPU card. Make sure that the settings of the Ethernet switch match the setup
file. See Chapter 5 for the configuration setup.
If the previous DPU was a DPU3, DPU4A, or DPU4B; new Ethernet
switches and cables will need to be installed. Consult the factory for details
about this type of upgrade.
In all upgrade situations, the backup cable must be replaced with a DPU4F
backup cable (Metso Automation # 050292).
Mounting Procedures
Before mounting any hardware, refer to the cabling and field wiring sections
of Publication 278596,
maxPAC Hardware Reference Guide, and
Publication
278563,
Model IOP Input/Output System Installation and Preparation
.
To install the DPU in the rack, refer to Chapter 7
Starting the DPU
.
DPU Front Panel Controls and Features
All DPU controls, indicator LEDs, and push button switches are accessible
from the DPU’s front panel. Use this front panel to monitor or control
different aspects of the DPU. There are no internal switches or jumpers to be