2.9 Create a chain of requests to scan all the registers you want to poll from DA
-
TAWATCH.
2.10 Create register chain in your PLC configuration software and start to monitor or
control the parameters in your application.
The most common registers if 8 channels are used, please consult Metrix customer service for any ques
-
tion.
Parameter
Description
Type
Address
(Hex)
Address
(Decimal)
Channel.1.Main.Measured Value
Measured value
float32
0X1814
6164
Channel.1.Main.PV
The process variable (output) of the channel
float32
0X0100
256
Channel.1.Main.PV2
The secondary input process variable (ouput) of
the channel
float32
0X0110
272
Channel.2.Main.Measured Value
Measured value
float32
0X1894
6292
Channel.2.Main.PV
The process variable (output) of the channel
float32
0X0104
260
Channel.2.Main.PV2
The secondary input process variable (ouput) of
the channel
float32
0X0114
276
Channel.3.Main.Measured Value
Measured value
float32
0X1914
6420
Channel.3.Main.PV
The process variable (output) of the channel
float32
0X0108
264
Channel.3.Main.PV2
The secondary input process variable (ouput) of
the channel
float32
0X0118
280
Channel.4.Main.Measured Value
Measured value
float32
0X1994
6548
Channel.4.Main.PV
The process variable (output) of the channel
float32
0X010c
268
Channel.4.Main.PV2
The secondary input process variable (ouput) of
the channel
float32
0X011c
284
VirtualChannel.1.Main.ModbusInput
Modbus input value
float32
0X1c06
7174
VirtualChannel.2.Main.ModbusInput
Modbus input value
float32
0X1c86
7302
VirtualChannel.3.Main.ModbusInput
Modbus input value
float32
0X1d06
7430
VirtualChannel.4.Main.ModbusInput
Modbus input value
float32
0X1d86
7558