Power Network Application Trainer
– Power generator, transformer, coils
181
Expected result:
Where:
r
A
, r
B
, r
C
and ∆r
A
, ∆r
B
, ∆r
C
are turn ratio and relative error relateds to the nominal ratio;
i
A
, i
B
, i
C
and
ϕ
A
,
ϕ
B
,
ϕ
C
are primary excitation current and phase angle between
primary and secondary voltage (related to single voltage and not to the voltage vector
group).
Turn ratio is inside specified values, so there is PASS indication.
Hints:
- Measured values should not deviate more then 0.5 % from the nominal
ratio (according IEC 60076-1standard)
Exercise 2:
Setup switch Nm. 4 to position 2:
Method used
Simulated condition
Expected result
r
A
= 20.217
Ω,
∆
r = >100%, @ Uex =80V, fex= 70
Hz
r
B
= 10.089
Ω,
∆
r = 0.14%, @ Uex =80V, fex= 70 Hz
r
C
= > 8000
Ω,
∆
r = >100%, @ Uex =80V, fex= 70
Hz
Table 57-3: Transformer turn ratio measuring setup/result presentation with simulated error
Start the measurement by pressing START key
on the instrument or icon
on the LCD.
Expected result:
There is FAIL indication and additional warning, that there was problem during
measurements.
Содержание MI 3298
Страница 55: ...Power Network Application Trainer Earthing Grounding network impedance measurement 55 ...
Страница 56: ...Power Network Application Trainer Earthing Grounding network impedance measurement 56 ...
Страница 124: ...Power Network Application Trainer Earthing Grounding network impedance measurement 124 ...
Страница 228: ...MI 3290 Earth Analyser 228 ...
Страница 229: ...MI 3280 Digital Transformer Analyser 229 ...
Страница 230: ...MI 3280 Digital Transformer Analyser 230 ...
Страница 231: ...MI 3250 MicroOhm 10A 231 ...
Страница 232: ...MI 3205 TeraOhmXA 5kV 232 ...