MI 3110 EurotestIM
Instrument operation
23
4.4.6 Initial settings
In this menu the instrument settings,
measurement parameters and limits can be
set to initial (factory) values.
Figure 4.11: Initial settings dialogue
Keys:
/
Selects option [YES, NO].
TEST
Restores default settings (if
YES
is selected).
ESC
Exits back to settings menu.
Function selector
Exits back to main menu without changes.
Warning:
❑
Customized settings will be lost when this option is used!
❑
If the batteries are removed for more than 1 minute the custom made settings will
be lost.
The default setup is listed below:
Instrument setting
Default value
Language
English
Contrast
As defined and stored by adjustment procedure
Isc factor
1.00
Commander*
A1314, A1401
Test mode:
Function
Parameters / limit value
Sub-function
SINGLE TESTS:
Z - LINE
Fuse type: none selected
VOLTAGE DROP
ΔU: 4.0 %
Z
REF
: 0.00 Ω
ISFL
Limit: none
IMD
Type: AUTO R
Min. insulation resistance: 30 kΩ
Interval: 2 s
AUTO SEQUENCE:
Z - LINE
Fuse type: C
Rated current: 16 A
Disconnection time: 0.2 s
ISFL
Limit: 3.0 mA
IMD
Type: AUTO R
Min. insulation resistance: 35 kΩ
Interval: 2 s
* versions 3.x.xx and higher
Note
:
❑
Initial settings (reset of the instrument) can be recalled also if the
TAB
key is
pressed while the instrument is switched on.