5.8 Socket outlet test
The Socket outlet test is an alternative test method for performing Polarity / Correct
connections and PE conductor test on sockets as specified in the AS / NZS 3017.
A sequence of four tests is carried out automatically:
Resistance between L and N terminal
Resistance between L and PE terminal
Resistance between N and PE terminal
Resistance of PE conductor
The test can be carried out directly from the socket outlet without using the trailing lead.
All three test leads must be connected during the test. Usually the circuit is terminated
with the Resistance box (A 1195) at the switchboard side.
See chapter
4.1 Function selection
for instructions on
key functionality.
Figure 5.34: Socket test
Test parameters for socket test
LIMITS Rln, Rlpe,Rnpe
Resistances
[ No limit, socket Switch
ON
and Switch
OFF
]
LIMIT Rpe
Maximum resistance
[OFF, 0.1
Ω
÷ 20.0
Ω
]
Limits in option
Switch ON:
Resistance* R
LN
= 15
Ω
, R
LPE
= 10
Ω
, R
NPE
= 5
Ω
Limits in option
Switch OFF:
Resistance* R
LN
>1999
Ω
, R
LPE
>1999
Ω
, R
NPE
= 5
Ω
Allowed tolerances for PASS are +2.5
Ω
/ -1.5
Ω
Connections for Socket test
Figure 5.35: Socket test – connection of plug commander and universal test cable