MI 3309 DeltaGT
Technical specifications
20
Powered by..................... mains
Test current..................... ½
I
N
, I
N
, 5
I
N
(I
N
= 10 mA, 15 mA, 30 mA)
Start angle ...................... 0
, 180
, both
Test modes ..................... single, autotest
Test terminals
MAINS terminal
Specified accuracy is valid for complete operating range.
3.7.2 Portable RCD trip-out time
Range Resolution
Accuracy
0 ms
300 ms(½
I
N
)
0.1 ms
0 ms
300 ms (I
N
)
0.1 ms
3 ms
0 ms
40 ms (5
I
N
)
0.1 ms
1 ms
Powered by..................... mains
Test current..................... ½
I
N
, I
N
, 5
I
N
(I
N
= 10 mA, 15 mA, 30 mA)
Start angle ...................... 0
, 180
, both
Test modes ..................... single, autotest
Test terminals
Test socket – IEC test terminal
Specified accuracy is valid for complete operating range.
3.8 Power
Apparent power
Range Resolution Accuracy
0.00 kVA
4.00 kVA
0.01 kVA
(5 % of r 3 digits)
Powered by..................... mains
Test duration:............................ 2 s, 3 s, 5 s, 10 s, 30 s, 60 s, 120 s, --- s
Test terminals ........................... MAINS terminal
* Measurement is limited to 120 s if (I
load
> 10 A).
3.9 TRMS Voltage
Range
Resolution
Accuracy
80
300 V
1 V
(2 % of r 2 digits)
Frequency Indication
only.
Result type................................ True r.m.s.
Nominal frequency range.......... 0 Hz, 50 Hz
60 Hz
Frequency accuracy ................. Indication only
Test terminals ........................... MAINS terminal