Parameter Default Description
MIN... MAX
Temperature alarms
A0
0
Size selection for high/low temperature alarms
0=control temperature; 1=evaporation tem-
perature
A1
0.0
Low temperature alarm threshold
-99... 99 °C/°F
A2
0
Low temperature alarm type
0=disabled; 1=in relation to setpoint; 2=ab-
solute
A4
0.0
High temperature alarm threshold
-99... 99 °C/°F
A5
0
High temperature alarm type
0=disabled; 1=in relation to setpoint; 2=ab-
solute
A6
120
High temperature alarm delay from power-on
0... 240 min
A7
15
High/low temperature alarm delay
0... 240 min
A8
15
Post-defrosting high temperature alarm delay
0... 240 min
A9
15
High temperature alarm delay from door closure
0... 240 min
A10
10
Power failure duration for alarm memory storage
0... 240 min
A11
2.0
High/low temperature alarm reset differential
1... 15 °C/°F
A12
1
Type of power failure alarm notification
0=HACCP LED; 1=HACCP LED + label PF +
buzzer; 2=HACCP LED + label PF + buzzer (if
duration > A10)
Fans (part 1)
F0
1
Evaporator fan mode in normal operation
0=off; 1=on; 2=on if compressor on; 3=tem-
perature-controlled (with temperature con-
trol + F1); 4=temperature-controlled (with
temperature c F1) if compressor on;
5=function of F6; 6=temperature-controlled
(with F1); 7=temperature-controlled (with F1)
if compressor on
F1
-4.0
Evaporator fan adjustment threshold
-99... 99 °C/°F
F2
0
Evaporator fan mode in defrosting and drip mode
0=off; 1=on; 2=function of F0
F3
2
Maximum evaporator fan off time
0... 15 min
F4
30
Evaporator off fan time in energy saving
0... 240 s x 10
if F0≠5
F5
30
Evaporator on fan time in energy saving
0... 240 s x 10
if F0≠5
F6
0
High/low temperature operation
0=for low humidity (with F17 and F18 if com-
pressor off, on if compressor on); 1=for high
humidity (on)
F7
5.0
Evaporator on fan threshold from drip ( in relation to
setpoint)
-99... 99 °C/°F
se F7
F8
2.0
Evaporator fan adjustment threshold differential
1... 15 °C/°F
F9
10
Evaporator off fan delay from compressor off
0... 240 s
if F0= 2 or 5
F10
1
Condenser fan mode
0=temperature-controlled (with F11); 1=tem-
perature-controlled (with F11) if compressor
off, on if compressor on; 2=temperature-con-
trolled (with F11) if compressor off, on if
compressor on, off in defrosting, pre-drip and
drip
Содержание 4247252
Страница 27: ...Huomautuksia ...
Страница 28: ......
Страница 29: ...MANUAL GASTRONOMISKÅP EVJ SV MANUAL FÖR ANVÄNDNING OCH UNDERHÅLL GASTRONOMISKÅP EVJ ...
Страница 55: ...Anmärkningar ...
Страница 56: ......
Страница 57: ...GASTRONOMY EVJ CABINET MANUAL EN USE AND MAINTENANCE MANUAL GASTRONOMY CABINET EVJ215 ...
Страница 83: ......
Страница 84: ...BN6LIBV003 ...