UNT Controller—Unitary Controller (UNT) 31
The AI switches should be factory set with AI 1, 2, and 3 as resistive
inputs, and AI 4, 5, and 6 as 0 to 10 VDC inputs. You may reconfigure the
switches by using the following table. For example, if you connect a
10 VDC input to AI 4, set SW1-4 to Off and SW2-4 to On.
Table 10: Analog Input DIP Switch Settings
Hardware
Point
Temp (Resistive
Input)
2 VDC (0 to
2 VDC Input)
10 VDC (0 to
10 VDC Input)
Switch
SW1
SW2
SW1
SW2
SW1
SW2
AI 1
ON
OFF
OFF
OFF
OFF
ON
AI 2
ON
OFF
OFF
OFF
OFF
ON
AI 3
ON
OFF
OFF
OFF
OFF
ON
AI 4
ON
OFF
OFF
OFF
OFF
ON
AI 5
ON
OFF
OFF
OFF
OFF
ON
AI 6
ON
OFF
OFF
OFF
OFF
ON
Four binary inputs on the controller are located in the center of the
terminal strip.
The binary inputs on the UNT110/111, 120/121, and 140/141 series
controllers are inactive when open or connected to UNT common. When a
binary device closes to complete a binary circuit, the binary input provides
the 24 VAC which, in turn, activates the input. Binary inputs have a
threshold between 5 VAC and 18 VAC. BI 4 may be used as an
accumulator input for frequencies less than 2 Hz.
Binary outputs are triacs on the controller hardware. The controller has
either six or eight binary outputs. These outputs switch 24 VAC to the
output.
For the UNT110/111, UNT120/121, and UNT140/141 series controllers,
use the terminal labeled TRIACS when using a separate load transformer.
Remove the high side/low side triac jumper on the UNT110/111,
UNT120/121, and UNT140/141 for this application (see Figure 8). For
important power and load specifications, see Table 5.
The terminal labeled TRIACS on the UNT110/111 and UNT120/121
series controllers is the internal shared node of each triac output
(see Figure 13). When connecting this terminal (via the wire jumper) to
24 VAC for high side switching, each load must be connected between the
binary output terminal and any common terminal. When connecting this
terminal to common for low side switching, each load must be connected
between the binary output terminal and any 24 VAC terminal.
Binary Inputs
Binary Outputs
(Triac Jumper
Information)
UNT110/111 and
UNT120/121
Содержание UNT Series
Страница 4: ...4 UNT Controller Unitary Controller UNT ...
Страница 10: ...10 UNT Controller Unitary Controller UNT ...
Страница 60: ...60 UNT Controller Unitary Controller UNT ...
Страница 78: ...78 UNT Controller Unitary Controller UNT ...
Страница 90: ...90 UNT Controller Unitary Controller UNT ...
Страница 95: ...UNT Controller Unitary Controller UNT 95 Notes ...