Programming—IFC-1010/2020 Programming
L3D64
A1P12
A9P2
Z23
First
Annunciator
Point
Dummy
Zone
Second
Annunciator
Point
Smoke
Detector
fig 52.cdr
Figure 42: Mapping an Annunciator Point
Prog
#
3
^
6
????
Level 2 Password
sec136a
Figure 43: Key Sequence to Access Option 6
(Cooperative Control-By-Event)
Option 6 of the Partial Point Programming menu allows the programmer to
change the CCBE for any reverse activated zone when using the
IFC-1010/2020 with the Metasys Fire Network.
* This item is a Metasys Fire Network-specific function and
isprogrammed only if a SIB-NET is used.
N7
Note: A software zone is not a physical zone, but rather a software
grouping in control panel memory.
When programming a particular reverse zone, the control panel prompts
the programmer with:
ENTER COOPERATIVE CONTROL-BY-EVENT :
The following CRT screen display illustrates CCBE programming for
reverse zone number 220 to be activated by other zones on the Metasys
Fire Network nodes.
PRESS 1=TYPID,2=CBE,3=LBL,4=OPTNS,5=AMAP,6=CCBE : 6
ENTER LXX(D/M)YY, ZXXX OR AXXPYY FOR PT. INSTALL (BCKSPC TO ABORT) : Z220
ENTER COOPERATIVE CONTROL-BY-EVENT :
OR(N8Z1 N8Z2 N8Z3 N8Z4 AND(N9Z1 N9Z2 N9Z3 N9Z4) AND(N10Z1 N10Z2 N10Z3 N10Z4))
For a complete description of the types, parameters, limitations, and
guidelines of CCBE programming, see the
Control-By-Event
Programming
section in this document.
Cooperative
Control-By-
Event*
6=CCBE