Preliminary—This information may change.
Miscellaneous—Emergency Stations (AFAWS-Series)
9
Assembly of Units with
Armored Cable Handsets
This assembly procedure is for telephones with armored cable handsets.
Complete the following steps when the enclosure has been mounted and
the system wiring is in place (refer to Figure 3).
1.
Attach system wiring to the terminal strip on the telephone chassis
assembly. See Figure 2 or 3.
2.
Install 6-32 nut in backbox. Do not tighten.
3.
Inset armored cable end into slot on top of telephone chassis assembly.
4.
Install telephone chassis assembly in backbox.
5.
Install trim ring on backbox with 6-32 wing nuts. Do not tighten.
Notes: Telephone circuits are supervised and power-limited.
Use twisted pair shielded cable for telephone circuit wiring. For
best operation, terminate shield at FFT-7/S 24V power supply
common (-).
Maximum telephone circuit wire resistance is 40 ohms.
For ELR connection to devices with terminals, use Resistor 71252.
For ELR connection to devices with flying leads, use
Resistor 71245. In Canada, N-ELR Resistor Assembly is required.
Refer to the fire panel manual for UL power-limited requirements
and further information.