Troubles Solutions

Operation

This is a normal situation 
caused by the short suction of 
water by the internal pressure 
of the refrigerator

The refrigerator makes too 
much noise even being in 
operation for some time.

Consult the item
"Installation"

Even with little frequency of 
opening of the door and the 
correct distribution of bottles, 
the same ones don't reach the 
refrigeration temperature

Opening very
frequent door

Distribute the bottles again 
avoiding excessive quantities 
of bottles

Procedures

Possible causes

Inspect

Troubles

Low current

If the electric installation is in 
order, install a voltage
automatic regulator with
saturated nucleus not smaller
1000 VA

Temperature indicator power
on indicating the temperature
but the lamps are without
energy

Incorrect installation

Very noisy
refrigerator

Avoid to open the doors 
without necessity

The refrigerator produces 
something noise after opening 
up the door

Excess of bottles or 
non appropriate 
distribution

High internal
temperature

Check the main switch is
power on, check the fuses or
automatic breaker, if they are 
in order transfer if it possible
the beer

Shortage of current
or out main switch

Temperature
indicator power off

The refrigerator
doesn't work

Temperature indicator power
on indicating the temperature
of the product

High current

Install a voltage automatic
regulator with saturated
nucleus not smaller 1000 VA

Even with little frequency of
opening of the door, the bottles
don´t reach the refrigeration
temperature

With frequent opening of the 
door, the bottles don't reach 
the refrigeration temperature

Incorrect installation

After a period of operation 
lack, the refrigerator makes 
some noise during the 
beginning of its operation

This is a normal 
situation if the 
refrigerator was not 
used by some time

The refrigerator micro-processed controller is responsible the following functions: 

1 COMPRESSOR COMMAND  

The controller turns off the compressor when the internal temper ature reaches the adjustment point, fastening it again when over coming 
the differential. For example, a controller with a adjustment po int is -3,5° C and a differential of       1  ° C.  The compressor will turn off to 
-3,5° C the compressor will turn off when defrost is  actived too, and  still turned off by a non inferior period of 90 secon ds after connected 
the unit. This retard has the objective of increasing the useful life of compressor. In event of flaw of sensor the compressor w ill stop 
immediately and an alert will be shown in temperature indicator  ( consult temperature indicator alerts ).

2 DEFROST  

The controller executes automatically a cycle defrost after to b e connected the unit and every 8 hours of 
operation. the purpose of cycle defrost when is connected the re frigerator, is to avoid the excessive 
accumulation of ice in energy supply flaw, the controller restar t the operation time when being disabled. 

For example: supposing that 6 hours of operation have passed ( l acking only 2 hours for next defrost ) and happens 
a energy supply flaw. 

When losing the controller the registration of lapsed time, imme diately it will execute a defrost cycle, so the user doesn't 
need to wait 8 hours for next defrost. The defrost cycle will be concluded when the evaporator reaches the temperature of 
+15°C., the internal temperature be up of +30 °C or measured by time, 20 minutes after defrost cycle has conclu ded 
(whatever happens first). When the refrigerator is connected and the temperature of evaporator is up +15 °C, the defrost 
system will remain disabled. In case defrost sensor failure, an  alert will be shown by the temperature indicator (consult 
temperature indicator alert)

3 TEMPERATURE INDICATOR ALERT

Alert

Meaning

Led turned-off

Compressor and defrost resister disabled

Led turned- on

Defrost cycle in process

Led blinking

Compressor in process

Alert “ 88 “

Internal temperature less than -10 ° C or cabinet sensor damaged

( opened )

Alert “ 99 “

blinking

Internal temperature major than 50° C or cabinet sensor damaged

( short-circuit ) 

Alert “ 00 “

Defrost sensor damaged

Alert

Meaning

Led turned-off

Compressor and defrost resister disabled

Led turned- on

Defrost cycle in process

Led blinking

Compressor in process

Alert “ 88 “

Internal temperature less than -10 ° C or cabinet sensor damaged

( opened )

Alert “ 99 “

blinking

Internal temperature major than 50° C or cabinet sensor damaged

( short-circuit ) 

Alert “ 00 “

Defrost sensor damaged