5. COMMISSIONING
INSTALLING THE FLUX IO-Link in an IO-Link NETWORK
5.1 IODD CONFIGURATION FILE
The corresponding “MetalWork-FLUX-_ _ _ _ _ _ _ _ _-IODD1 1” IODD configuration file available on the Metal Work
website is supplied with the FLUX IO-Link.
5.2 ADDRESSING
5.2.1 Cyclic data
• 4 input bytes for the measured flow [Nl/h]
• 2 input bytes for measured pressure [mbar]
• 1 input byte for status indication (digital switch)
• 1 input byte for diagnostics.
Function
Data type
Address
Flow Nl/h DWord
%ID0
Pressure mbar Word
%IW4
Digital output
Byte (bit 0)
%I5.0
Diagnostics
Byte
%IB6
5.2.2 Acyclic data
Function
Index
Subindex
Description
Data type
Format
Temperature °C 100
0
Temperature
°C Read 2 byte
Hex
Flow Nl/min
101
0
Flow
Nl/min Read 2 byte
Hex
Flow Nl/h
102
0
Flow
Nl/h Read 4 byte
Hex
Flow Nm
3
/min
103
0
Flow
Nm
3
/min Read 4 byte
Hex
Flow Nm
3
/h
104
0
Flow
Nm
3
/h Read 4 byte
Hex
Flow ft
3
/min
105
0
Flow
ft
3
/min Read 4 byte
Hex
Flow ft
3
/h
106
0
Flow
ft
3
/h Read 4 byte
Hex
Volume consumption
Nl 107
0
Volume consumption
Nl Read 4 byte
Hex
Energy consumption
kWh 108
0
Energy consumption
kWh Read 4 byte
Hex
Mass consumption
kg 109
0
Mass consumption
kg Read 4 byte
Hex
Mass flow rate
gr/min 110
0
Mass flow rate
gr/min Read 2 byte
Hex
Power
W 111
0
Power
W Read 2 byte
Hex
Series FLUX
112
0
1 = FLUX 1
2 = FLUX 2
Read 1 byte
Hex
Display
113
0
0 = Not present
1 = Present
Read 1 byte
Hex
Pressure sensor
115
0
0 = Not present
1 = Present
Read 1 byte
Hex
Alarms
116
0
0 = No alarms
1 = Alarm
Read 1 byte
Hex
Consumption reset
02
0
Value = DEC 160
Hex 0xA0
Write 1 byte
Hex