1. Safety Precautions 

 
ALWAYS EMPLOY SAFE WORKING 
PRACTISE AND PROCEDURES 

 

  WARNING: 

Risk of Danger 

 

  WARNING: 

Risk of Electric Shock 

 

  WARNING: 

Risk of High Pressure 

 

 

WARNING: 

Consult Manual 

 

When installing, commissioning, operating or 
carrying out service or maintenance on a product, 
personnel must use safe working practise and 
observe all relevant local health and safety 
requirements and regulations. Attention of users in 
the UK is drawn to the Health and Safety at Work 
Act, 1974, and to the Regulations and 
Recommendations of the Institution of Electrical 
Engineers (IEE). 

 

Lethal voltages are used within the product. Use 
extreme caution when carrying out electrical 
checks. Isolate the power supply before starting 
any maintenance work. 

 

It is not possible to anticipate every circumstance 
that might represent a potential hazard. If the user 
employs an operating procedure, an item of 
equipment or a method of working which is not 
specifically recommended the user must ensure the 
product will not be damaged or made unsafe and 
that there is no risk to persons or property. Failure 
to observe safety precautions or implement safe 
working practises may be considered dangerous 
practice or misuse of the product. 
 

1.2 Installation 

 

Installation work must only be carried out by a 
competent person under qualified supervision. 

 

A fused isolation switch must be fitted between the 
main power supply and the product. 

 

The product should be mounted in such a location 
as to allow operational and maintenance access 
without obstruction or hazard and to allow clear 
visibility of indicators at all times. 

 

If raised platforms are required to provide access to 
the product they must not interfere with normal 
operation or obstruct access. Platforms and stairs 
should be of grid or plate construction with safety 
rails on all open sides. 
 

1.3 Operation 

 

The product must only be operated by competent 
personnel under qualified supervision. 

 

Never remove or tamper with safety devices, 
guards or insulation materials fitted to the unit. 

 

The product must only be operated at the supply 
voltage and frequency for which it is designed. 

 

When mains power is switched on, lethal voltages 
are present in the electrical circuits and extreme 
caution must be exercised whenever it is necessary 
to carry out any work on the unit. 

 

Do not open access panels or touch electrical 
components while voltage is applied unless it is 
necessary for measurements, tests or adjustments. 
This work must only be carried out by a qualified 
electrician or technician equipped with the correct 
tools and appropriate protection against electrical 
hazards. 

 

All air compressors and/or other machine 
equipment connected too, and controlled by, the 
product should have a warning sign attached 
stating ‘THIS UNIT MAY START WITHOUT 
WARNING' next to the display panel.  

 

If an air compressor and/or other machine 
equipment connected too, and controlled by, the 
product is to be started remotely, attach warning 
signs to the machine stating ‘THIS UNIT CAN BE 
STARTED REMOTELY’ in a prominent location, 
one on the outside of the machine, the other inside 
the machine control compartment. 

 
1.3 Service Maintenance and Repair 

 

Service, maintenance, repairs or modifications 
must only be carried out by competent personnel 
under qualified supervision. 

 

If replacement parts are required use only genuine 
parts from the original equipment manufacturer, or 
an alternative approved source. 

 

Carry out the following operations before opening 
or removing any access panels or carrying out any 
work on the product:- 

 

 

Isolate from the main electrical power supply. 
Lock the isolator in the 'OFF' position and 
remove the fuses. 

 

Attach a label to the isolator switch and to the 
product stating ‘WORK IN PROGRESS - DO 
NOT APPLY VOLTAGE'. Do not switch on 
electrical power or attempt to start the unit if 
such a warning label is attached. 

 

Ensure that all instructions concerning operation 
and maintenance are strictly followed and that the 
complete product, with all accessories and safety 
devices, is kept in good working order. 

 

The accuracy of sensor devices must be checked 
on a regular basis. They must be renewed when 
acceptable tolerances are exceeded. Always 
ensure any pressure within a compressed air 
system is safely vented to atmosphere before 
attempting to remove or install a sensor device. 

 

The product must only be cleaned with a damp 
cloth, using mild detergents if necessary. Avoid the 
use of any substances containing corrosive acids or 
alkalis. 

 

Do not paint the control facial or obscure any 
indications, controls, instructions or warnings.

 

Содержание DCO

Страница 1: ...MANY0913B GB Metacentre DCO Technical Manual 28 02 2016 TM DCO Duty Change Over bar...

Страница 2: ...al Features and Functions 6 0 Menus and Navigation 6 1 To Access a Menu 6 2 Menu Item Adjustment 6 3 To Exit a Menu 6 4 Menu map 7 0 Operation 7 1 User Interface 7 2 Compressor Identification 7 3 Comp...

Страница 3: ...sent in the electrical circuits and extreme caution must be exercised whenever it is necessary to carry out any work on the unit Do not open access panels or touch electrical components while voltage...

Страница 4: ...mpressor Connections and Control 1 2 3 1 2 3 T M DCO Each air compressor in the system can be integrated with the Metacentre DCO using an interface module supplied with DCO Kit that is designed to ena...

Страница 5: ...the urgency or time limit and the acceptable deviation of system pressure the Tolerance from the normal control limits PH PL PT a b c The same method is implemented in reverse above the High Pressure...

Страница 6: ...ion capacity If an increase in the tolerance band is insufficient the DCO s dynamic reaction response can be influenced by increasing the Damping factor DA reducing tendency to over react The Damping...

Страница 7: ...or non proffered compressor s Rotation Each time the set rotation interval elapses a sequence rotation occurs and the sequence assignment for each compressor is re arranged The compressor that was ass...

Страница 8: ...s only required as an emergency backup compressor number 4 it may be desirable to ensure the preferred compressor is always utilised first and the non preferred compressor utilised last in any sequenc...

Страница 9: ...ystem pressure sensor For use in Pollution Degree 2 Environment Type 12 12 K or 13 cable glands conduit or other cable entry fittings must be used to maintain Type 12 rating of the unit Before opening...

Страница 10: ...h connection to the unit s earth as illustrated must be implemented The AWG size of the earth connection must be the same as the incoming supply wires The applied torque for fixing must be at least 1...

Страница 11: ...sing an mi PCB the signal wires must be connected to the DCO terminals dedicated for the assigned compressor reference number 3 2 1 8 7 4 5 6 R1 35mm DIN 76 34 28 The mi PCB is a 35mm DIN rail mountab...

Страница 12: ...essor as ready and available for utilisation as required regardless of actual compressor status 4 6 2 Option B Alarm Metacentre DCO menu 3 Set the Alarm Input Option for the compressor to 0 1 8 7 For...

Страница 13: ...he compressor to start and run within 30 seconds of a Load command is sufficient to assume the compressor is not available due to being manually stopped or in a shutdown Alarm state Dependant on the c...

Страница 14: ...contacts of which can be used to regulate the compressor in accordance with Metacentre DCO pressure control Ensure the compressor is equipped with independent excess pressure protection The mi PCB co...

Страница 15: ...Pressure switch settings near or below the Metacentre DCO pressure settings will disrupt successful pressure control 4 7 3 3 Wire Pressure Switch For an air compressor fitted with a 3 wire electro me...

Страница 16: ...ta communications and other low voltage signals can be subject to electrical interference This potential can result in intermittent malfunction or anomaly that is difficult to diagnose To avoid this p...

Страница 17: ...naccurate check the type and range of the sensor and carry out the pressure sensor commissioning and calibration procedure Menus and Navigation Menu Items 4 Po Sensor Offset Calibration 4 Pr Sensor Ra...

Страница 18: ...will be displayed If the access code is not recognised the display will return to normal operation 6 2 Menu Item Adjustment When in menu mode the upper display will show the menu number followed by t...

Страница 19: ...essure band 1 HA High Pressure Alarm High pressure Alarm level This function remains active at all times Set just below system pressure relief value s and below the maximum system pressure rating of a...

Страница 20: ...ndition is true The relay contacts will open circuit during a loss or disruption to the DCO power supply regardless of setting 4 r2 Auxiliary Output Relay 2 Function Determines the function of Relay O...

Страница 21: ...ge to 15 0bar Note The range value equates to the maximum value not the scope of the sensor Execute the calibration procedure 2 Calibration Procedure a Offset Expose the sensor to atmosphere and adjus...

Страница 22: ...C3 C4 Compressor sequence assignment is indicated by letters A Duty B First Standby C Second Standby D Third Standby The first letter in the sequence is the duty assignment for compressor 1 example C1...

Страница 23: ...r loss occurred The DCO will not automatically restart if the DCO was in a stopped state when the power disruption or loss occurred 7 10 Failure Mode If the DCO experiences a disruption to normal cont...

Страница 24: ...Data Dimensions 253mm x 160mm x 90mm 10 x 6 3 x 3 6 Weight 2 7kg 6lb Mounting wall 2 x screw fixings Enclosure IP54 NEMA 12 UL Type 12 Supply 115 to 230Vac 10 50 60Hz Power 60VA Temperature 0 C to 46...

Страница 25: ...2 X10 T1 6A PSU IEC 20 x 5mm LED1b N L E 0VDC VDC X09 X08 RL1 RL2 C01 C018 RT1 X07 X06 X05 X04 X01 LCD Ai1 C Comp 1 Comp 2 Comp 3 Di GND LOAD Comp 4 R1 R2 115 230Vac 60VA 50 60Hz Di GND LOAD Di GND LO...

Страница 26: ...oad GND Di Load GND Di Load 0VDC 24V DC D3 0V DC 24V DC D2 0VDC 24V DC D1 Comp 1 1 mi PCB Comp 2 Comp 3 Comp 4 24V DC A i1 2 mi PCB 3 mi P CB 4 mi PCB 115 230Vac 60VA 50 60Hz E L N 1 2 3 4 1 2 3 1 2 3...

Страница 27: ...Technical Manual Page 26...

Страница 28: ...quire further technical assistance please contact your local dealer Stamp with name and address of local dealer Manufacturers Identification Compressor Machine Controls NV Industriepark De Bruwaan 37B...

Отзывы: