Mestek IIEB-11 Скачать руководство пользователя страница 13

13

Figure 12 - Adaptor Installation

REFER TO SPECIFICATION TABLE AND INSTALLATION MANUAL FOR PROPER USAGE

The following instructions apply to Canadian installations in addition to installation and operating instructions:
1.   Installation must conform with local building codes, or in absence of local codes, with current CSA B149.1 installation codes for natural gas 

burning appliances and equipment, or CSA B149.2, installation codes for propane gas burning appliances and equipment.

2.   Any references to U.S. standards or codes in these instructions are to be ignored and the applicable Canadian standards or codes applied.
3.   The reducer must be fi eld supplied for 100, 125, 150 and 175 MBH unit sizes.
4.  If using a metal vent system under positive gauge pressure in Canada, a slip fi t vent connection must be secured by at least two corrosion-

resistant screws, or other mechanical locking means.

5.  The vent shall not terminate – (a) Less than 6 ft. (1.8m) from a combustion air inlet of another appliance. (b) Less than 3 ft. (1m) from any 

other building opening or any gas service regulator. (c) Directly above a gas utility meter or service regulator.

Use single wall pipe constructed of 26 gauge galvanized 
steel or material or equivalent durability and corrosion 
resistance for the vent system. For installation in 
Canada, vent pipe must conform with local building 
codes, or in absence of local codes, with current CSA 
B149.1/B149.2 installation codes for gas bur ning 
appliances and equipment.

 Never use a pipe of a diameter 

other than that specified in Table 1 or Figure 
2! Never use PVC or other nonmetallic pipe for 
venting! To do so may result in serious damage 
to the unit or severe personal injury or death!

The vent terminal must be installed with a minimum 
clearance of four feet (1.2m) from electric meters, gas 
meters, regulators and relief equipment.

Seal ALL vent pipe joints and seams to prevent 
leakage. Use General Electric RTV-108 or Dow-
Corning RTV-732 silicone sealant (or equivalent); or 3M 
#425 aluminum foil tape (or equivalent).

The vent system must be installed to prevent collection 
of condensate. Vertical vent pipes should be equipped 
with condensate drains. Pitch horizontal pipes 
downward 1/4 inch per foot (21mm per meter) toward 
outlet for condensate drainage (refer to Figures 9 
through 16).

Horizontal por tions of the venting system shall be 
supported at maximum intervals of four feet (1.2m) 
to prevent sagging (in Canada, support at 3 feet (1m) 
minimum intervals).

Insulate single wall vent pipe exposed to cold air or 
running through unheated areas.

Each unit must have an individual vent pipe and 
vent terminal per furnace section!
 Each unit MUST 
NOT be connected to other vent systems or to a 
chimney.

Units are shipped from the factory set up for vertical 
venting. To conver t the power venter for horizontal 
venting, remove the shipping support bracket; refer to 
Figures 9 thru 12 and 22, and follow this procedure:
 

1. Hold power venter motor in position.

 

2. Remove the three Phillips-head screws from the

          motor adaptor plate.
 

3. Remove the three screws which connect the  

 

  power venter stack to the power venter housing.

 

4. Rotate the power venter housing to the horizontal          

  position.
 

5. Replace screws accordingly.

NOTICE: The motor, pressure switch, and junction 
box bracket MUST remain located as shipped from 
the factory. Rotate only the blower housing! If the 
power venter housing is to be moved to the right 
horizontal position, the junction box must be rotated 
90 degrees CCW to clear the connection. To do this, 
remove all wires, conduit and conduit connector 
from the junction box, noting location of wires. Move 
box, using holes provided. Move 7/8 inch plug from 
bottom of box to side. Reconnect all wires according 
to the unit's wiring diagram.

Содержание IIEB-11

Страница 1: ...l operate and maintain unit in accordance with manufacturer s instructions to avoid exposure to fuel substances or substances from incomplete combustion which can cause death or serious illness The st...

Страница 2: ...bled high static pressure type centrifugal blower unit designed for heavy duty applications such as continuous operation or where a single unit heater must do the entire heating job in a large area Th...

Страница 3: ...ly with the general safety information may result in extensive property damage severe personal injury or death This product must be installed by a licensed plumber or gas fitter when installed within...

Страница 4: ...94 1295 1295 1226 1295 1295 E Hanging Distance Width 14 1 2 17 1 4 17 1 4 20 22 3 4 25 1 2 28 1 4 33 3 4 39 1 4 44 3 4 368 438 438 508 578 648 718 857 997 1137 F Discharge Opening Width 15 3 8 18 1 8...

Страница 5: ...as ignition system the unit heater must be installed such that the gas ignition control system is not directly exposed to water spray rain or dripping water NOTE Location of unit heaters is related di...

Страница 6: ...r and can actually drip water down from the unit heater onto floor surface Additional unit heaters should be installed if a minimum 50 F 10 C thermostat setting cannot be maintained AIR FOR COMBUSTION...

Страница 7: ...1 3 54 3 34 3 11 2 92 2 63 2 38 2 18 2 04 1 1 049 680 465 375 320 285 260 240 220 205 195 175 160 145 135 19 3 13 2 10 6 9 06 8 07 7 36 6 80 6 23 5 80 5 52 4 96 4 53 4 11 3 82 1 1 4 1 380 1400 950 770...

Страница 8: ...al gas applications install a pressure regulating valve in the line upstream from the main shutoff valve 3 Adequately support the piping to prevent strain on the gas manifold and controls 4 To prevent...

Страница 9: ...ER ASSEMBLY FOR THE 100 250 UNITS CONSISTS OF 1 WHEEL 1 HOUSING 1 SHAFT AND 1 BEARING SET FOR 300 400 UNITS THE BLOWER ASSEMBLY CONSISTS OF 2 WHEELS 2 HOUSINGS 1 SHAFT AND 1 BEARING SET Figure 7 Motor...

Страница 10: ...ase motors require a contactor or starter if specified 4 Motor frame must not exceed NEMA frame 56 Average value all speeds and frequencies 10 327 345 362 380 397 414 431 448 466 483 500 518 535 552 5...

Страница 11: ...re to disconnect power before servicing can cause severe personal injury or death Standard units are shipped for use on 115 volt 60 hertz single phase electric power The motor name plate and electrica...

Страница 12: ...16 for special installation requirements regarding these venting conditions CARBON MONOXIDE Your venting system must not be blocked by any snow snow drifts or any foreign matter Inspect your venting...

Страница 13: ...feet 1 2m from electric meters gas meters regulators and relief equipment Seal ALL vent pipe joints and seams to prevent leakage Use General Electric RTV 108 or Dow Corning RTV 732 silicone sealant or...

Страница 14: ...14 Figure 13 Figure 14...

Страница 15: ...15 Figure 15 Figure 16...

Страница 16: ...fan switch delays the operation of the fan until the heater is warmed then keeps the fan running after the gas has been turned off until the useful heat has been removed The start up fan delay must no...

Страница 17: ...4 BURNER SPRINGS 5 MAIN BURNER ORIFICE 6 TRANSFORMER 7 PILOT TUBING CONTROLS REFER TO UNIT WIRING DIAGRAM 8A MAIN GAS VALVE HONEYWELL 8B MAIN GAS VALVE WHITE RODGERS 9 HONEYWELL IGNITOR 10 HONEYWELL...

Страница 18: ...old pressure of 3 5 inches W C 0 9 kPa Adjustment of the pressure regulator is not normally necessary since it is preset at the factory However field adjustment may be made as follows a Attach manomet...

Страница 19: ...3 A proper pilot flame is a soft steady flame that envelopes 3 8 to 1 2 inch 9 5 to 12 7mm of the flame sensor tip 4 Replace the pilot adjustment cap PERIODIC SERVICE NOTICE It is recommended that the...

Страница 20: ...e and replace Refer to Operation 1 Close air shutter Refer to Operation 2 Check with local gas supplier for proper orifice size and replace Refer to Operation 1 Close air shutter 2 Reduce pilot gas Re...

Страница 21: ...and correct 5 Replace gas valve 6 Refer to Operation 1 Tighten all electrical connections 2 Adjust thermostat heat anticipator for longer cycles Refer to Operation 3 Check for proper air supply acros...

Страница 22: ...late rating check voltage replace fan motor if defective 4 Refer to label on motor 1 Check all wiring 2 Refer to H or N symptoms 3 Replace fan switch 1 Refer to Operation 2 This is especially true whe...

Страница 23: ...Check motor amps against motor name plate rating check voltage replace power venter motor if defective 4 Refer to label on motor 1 Check all wiring 2 Refer to H N symptoms 3 Replace venter relay X Pil...

Страница 24: ...e 20 Internal Furnace Components Figure 21 Burner Assembly Parts Figure 19 Component Parts Bottom View MOTOR GAS VALVE IGNITOR ELECTRIC LIGHTING INSTRUCTIONS DATA PLATE PILOT ACCESS DOOR OBSERVATION P...

Страница 25: ...400 units 6 dia flue outlet Increaser required To be supplied by manufacturer 25 REF NO DESCRIPTION 1 Blower Housing Assembly 2 Speed Nut 3 Motor 4 Washer Plain 5 Plate Adapter 6 Blower Wheel 7 Mounti...

Страница 26: ...from the Power Venter Blower Housing Item 8 6 Remove the Blower Wheel Item 9 from the motor shaft by removing the set screw Item 14 using a 1 8 Allen Wrench 7 Remove the three Motor Mounting Nuts Item...

Страница 27: ...uctions or has been altered or modified in any way by any unauthorized person b to any expenses including labor or material incurred during removal or reinstallation of the Product c to any damage due...

Страница 28: ...contact your wholesaler or rep DO NOT START this equipment unless you fully understand the controls GAS EQUIPMENT START UP GENERAL With power and gas off Make certain all packing has been removed Tigh...

Страница 29: ...1 HP w Contactor S 1 HP w Magnetic Starter G 1 1 2 HP w Contactor T 1 1 2 HP w Magnetic Starter H 2 HP w Contactor U 2 HP w Magnetic Starter J 1 4 HP W 1 4 HP w Magnetic Starter K 1 3 HP Y 1 3 HP w M...

Страница 30: ...NOTES 30...

Страница 31: ...NOTES 31...

Страница 32: ...260 NORTH ELM ST WESTFIELD MA 01085 TEL 413 568 9571 FAX 413 562 8437 www mestek com...

Отзывы: