29
USER´S MANUAL
ALARMS
Alarms Menu
ALRM.SET
Alarm Setup (Enable/Disable)
AUTO
Automatic search of C/K response value
AUTO.SET
Automatic Setup Sequence
BANK.PRE
Bank Pre-configuration Sequence Menu
BANK.TST
Bank Test: each step is automatically connected
and disconnected in turn. This facilitates testing of
the operation of each capacitor step contactor.
See also Step Test.
CIRC.A
Circular A stepping program
CIRC.B
Circular B stepping program
C/K
Response value, normally set up automatically by
the controller
CLR.STAT
Clear Statistics
COMMISS
Commissioning Sequence
Menu
COS PHI
Target cos
value
0,8ind
1.00
0,9cap
CT
Current Transformer primary setting, xxx/5 A
25/5
%
6000/5
DELAY
Safety Delay or reconnection delay. Response
10s
50s
600s
delay is fixed 20% of reconnection delay. The
default value corresponds to capacitors with
internal discharge resistors 50V 1 min
ENGLISH
Language names: English, for instance
ERR NN
Error in parameter search or verify. NN= error number
FACTOR.S
Restore Factory Settings
IGNORED
The controller does not require the information
about step sequence for any program outside
Optimal. The controller defines it automatically.
I HIGH
Current too high
>115%
I
N
I LOW
Current too low
<2,5%
I
N
LANGUAG
Language Selection for menus
LL
Line to Line connection
LN
Line to Neutral connection
LV
Low Voltage
MAINTEN
Maintenance Menu
MAN.SET
Manual Setup Sequence Menu
MANUAL
Manual setting of C/K response value. See further 0,01 0,50 1,99
MEASURE
Measurements
Menu
7. Glossary
Display
information
Long form text
Min
value
Default
value
Max
value
Содержание Varlogic NR12
Страница 1: ...Varlogic NR6 NR12 Power factor controller User manual...
Страница 12: ...12 USER S MANUAL Figure 9 Bank pre configuration...
Страница 16: ...16 USER S MANUAL Figure 12 Manual setup of parameters...
Страница 21: ...21 USER S MANUAL Figure 16 1 Maintenance menu...
Страница 22: ...22 USER S MANUAL Figure 16 2 Maintenance menu...
Страница 28: ...28 USER S MANUAL Figure 23 HV use of the controller...