9. Specifications:
The Interface is for use in low voltage, class 2 circuits only.
Primary power:
12 to 24Vdc ±10%, 550mA maximum (plus reader current)
12Vdc @ 450mA (plus reader current) nominal
24Vdc @ 270mA (plus reader current) nominal
Outputs:
6 outputs, Form-C, 5A @ 28Vdc, resistive
Inputs:
8 unsupervised/supervised, standard EOL: 1k/1k ohm, 1% 1/4 watt
2 unsupervised, dedicated for cabinet tamper and UPS fault
monitoring
Reader interface:
Reader power:
12Vdc ±10% regulated, 125mA maximum each reader
(jumper selectable and input voltage (VIN) must be 20Vdc minimum)
or
12 to 24Vdc ±10% (input voltage passed through) 125mA
maximum each reader
Reader LED output:
TTL compatible, high > 3V, low < 0.5V, 5mA source/sink
maximum
Reader buzzer output:
Open collector, 5Vdc open circuit maximum, 10mA sink
maximum
Reader data inputs:
TTL compatible inputs or 2-wire RS-485
Communication:
RS-485, 2-wire 9600, 19200, 38400 or 115200bps
Cable requirements:
Power:
18AWG, 1 twisted pair
RS-485:
24AWG, 120 ohm impedance, twisted pair with shield, 4,000'
(1,200m) maximum
Alarm inputs:
1 twisted pair per input, 30 ohms maximum
Outputs:
As required for the load
Reader data (TTL):
6 conductors, 18AWG, 500 feet (150m) maximum
Reader data (RS-485):
24AWG, 120 ohm impedance, twisted pair with shield, 4,000'
(1,200m) maximum
Mechanical:
Dimension:
6" (152mm)W x 8" (203mm)L x 1" (25mm)H
Weight:
11 oz. (312g) nominal
Environment:
Temperature:
-55°C to +85°C, storage
0°C to +70°C, operating
Humidity:
0% to 95% RHNC