9.  Specifications: 

The Interface is for use in low voltage, class 2 circuits only. 
 
Primary power: 

12 to 24Vdc ±10%, 550mA maximum (plus reader current) 
12Vdc @ 450mA (plus reader current) nominal 
24Vdc @ 270mA (plus reader current) nominal 

 
Outputs:  

6 outputs, Form-C, 5A @ 28Vdc, resistive 

 
Inputs: 

8 unsupervised/supervised, standard EOL: 1k/1k ohm, 1% 1/4 watt 
2 unsupervised, dedicated for cabinet tamper and UPS fault 
monitoring 

 
Reader interface: 

Reader power: 

12Vdc ±10% regulated, 125mA maximum each reader 
(jumper selectable and input voltage (VIN) must be 20Vdc minimum) 
or 
12 to 24Vdc ±10% (input voltage passed through) 125mA  
maximum each reader 

Reader LED output:  

TTL compatible, high > 3V, low < 0.5V, 5mA source/sink  
maximum 

Reader buzzer output: 

Open collector, 5Vdc open circuit maximum, 10mA sink  
maximum 

Reader data inputs: 

TTL compatible inputs or 2-wire RS-485 

 
Communication: 

RS-485, 2-wire 9600, 19200, 38400 or 115200bps 

 
Cable requirements: 

Power: 

18AWG, 1 twisted pair 

RS-485: 

24AWG, 120 ohm impedance, twisted pair with shield, 4,000' 
(1,200m) maximum 

Alarm inputs: 

1 twisted pair per input, 30 ohms maximum 

Outputs: 

As required for the load 

Reader data (TTL): 

6 conductors, 18AWG, 500 feet (150m) maximum 

Reader data (RS-485): 

24AWG, 120 ohm impedance, twisted pair with shield, 4,000' 
(1,200m) maximum 

Mechanical: 

Dimension: 

6" (152mm)W x 8" (203mm)L x 1" (25mm)H 

Weight: 

11 oz. (312g) nominal 

 
Environment: 

Temperature: 

-55°C to +85°C, storage 
0°C to +70°C, operating 

Humidity: 

0% to 95% RHNC 

 

 

Содержание MR52

Страница 1: ...ay be used for strike control or alarm signaling Eight supervised inputs are provided for monitoring the door contact exit push button and alarm contacts Communication to the MR52 is accomplished via...

Страница 2: ...RS 485 interface Power to the reader is selectable 12Vdc or input voltage passed through PT 125mA maximum per reader port This selection is made via jumper J2 and is made for both reader ports For th...

Страница 3: ...t be used The following two circuits are recommended Locate the protection circuit as close to the load as possible within 12 inches 30cm as the effectiveness of the circuit will decrease if it is loc...

Страница 4: ...N OFF ON Address 13 OFF ON ON ON OFF Address 14 OFF ON ON ON ON Address 15 ON OFF OFF OFF OFF Address 16 ON OFF OFF OFF ON Address 17 ON OFF OFF ON OFF Address 18 ON OFF OFF ON ON Address 19 ON OFF ON...

Страница 5: ...port 1 LED Input Status IN1 2 LED Input Status IN2 3 LED Input Status IN3 4 LED Input Status IN4 5 LED Input Status IN5 6 LED Input Status IN6 7 LED Input Status IN7 8 LED Input Status IN8 TMP Cabinet...

Страница 6: ...ge passed through 125mA maximum each reader Reader LED output TTL compatible high 3V low 0 5V 5mA source sink maximum Reader buzzer output Open collector 5Vdc open circuit maximum 10mA sink maximum Re...

Страница 7: ...other warranties or implied warranties and expressly excludes and disclaims all implied warranties of merchantability or fitness for a particular purpose Returned units are repaired or replaced from a...

Отзывы: