Jumpers: 

JUMPER 

DESCRIPTION 

J1 

RS-485 termination, install in first and last units only 

J2 

Not used 

J3 

2-wire/4-wire select, install in 2W position only 

J4 

Factory use only 

J5 

Factory use only 

J6 

Factory use only 

J7 

Factory use only 

J8 

Factory use only 

J9 

Factory use only 

 
 

7.  Status LEDs: 

Power-

up:  All LED’s OFF 

 

Initialization:

  Once power is applied, initialization of the module begins 

 
When initialization is completed, LEDs A, B, CT, and BA are briefly sequenced 

ON

 then 

OFF

 

Run time

:  After the above sequence, the LEDs have the following meanings: 

 

A LED

:  Heartbeat and On-Line Status: 

Off-line:  1 sec rate, 20% 

ON

 

On-line: 

Non-encrypted communication:  1 sec rate, 80%

 ON

 

Encrypted communication: 
.1 sec 

ON

, .1 sec 

OFF

, .1 sec 

ON

, .1 sec 

OFF

, .1 sec 

ON

, .1 sec 

OFF

, .1 sec 

ON

, .3 sec 

OFF 

 
A LED Error Indication:

 

Waiting for application firmware to be downloaded: .1 sec 

ON

, .1 sec 

OFF

 

B LED

:  SIO Communication Port Status: 

Indicates communication activity on the SIO communication port 

 

CT

:  Cabinet Tamper 

BA

:  Power Fault 

 
 

LED 1 

through

 16:

  Illuminates when output relay OUT 1 (K1), OUT 2 (K2) is energized and so on. 

 
 

 