background image

 

Mercury Security © 2018 

LP1501 

DOC  10107-0064 

REV 1.01 

 Page   6  

8.  Input Circuit Wiring: 

Typically, these inputs are used to monitor door position, request to exit, or alarm contacts.  Input circuits 
can  be  configured  as  unsupervised  or  supervised.    When  unsupervised,  reporting  consists  of  only  the 
open or closed states. 

When configured as supervised, the input circuit will report not only open and closed, but also open circuit, 
shorted, grounded*, and foreign voltage*.  A supervised input circuit requires two resistors be added to the 
circuit to facilitate proper reporting.  The standard supervised circuit requires 1k ohm, 1% resistors and 
should  be  located  as  close  to  the  sensor  as  possible.    Custom  end  of  line  (EOL)  resistances  may  be 
configured via the host software. 

*

 Grounded and foreign voltage states are not a requirement of UL 294 and therefore not verified by UL. 

The input circuit wiring configurations shown are supported but may not be typical:  

 
 

 

9.  Relay Circuit Wiring: 

Two Form-C contact relays are provided for controlling door lock mechanisms or alarm signaling devices.  
The relay contacts are rated at 2 A @ 30 Vdc, dry contact configuration.  Each relay has a Common pole 
(C), a Normally Open pole (NO) and a Normally Closed pole (NC).  When you are controlling the delivery 
of power to the door strike, the Normally Open and Common poles are used.  When momentarily removing 
power to unlock the door, as with a mag lock, the Normally Closed and Common poles are used.  Check 
with local building codes for proper egress door installation. 

Door  lock  mechanisms  can  generate  EMF  feedback  to  the  relay  circuit  that  can  cause  damage  and 
premature failure of the relay plus affect the operation of the LP1501.  For this reason, it is recommended 
that either a diode or MOV (metal oxide varistor) be used to protect the relay.  Wire should be of sufficient 
gauge to avoid voltage loss. 

 

From the Auxiliary output, the LP1501 can provide 12 Vdc power for external devices provided that the 
maximum current is not exceeded.  See the specifications section for details.  If a local power supply is 
used, it must be UL Listed Class 2 rated. 

 

 

1K,1%

1K,1%

1K,1%

1K,1%

Standard Supervised Circuit,
Normally Closed Contact

Standard Supervised Circuit,

Normally Open Contact

Unsupervised Circuit,
Normally Open Contact

Unsupervised Circuit,
Normally Closed Contact

IN2

IN1

TB1

1

 

Diode Selection: 
 

Diode current rating: 1x strike current 
Diode breakdown voltage: 4x strike voltage 
For 12 Vdc or 24 Vdc strike, diode 1N4002 
(100V/1A) typical. 

 

TB5

2-C

NC

NC
NO

1

NO
1-C

Содержание LP1501

Страница 1: ...TTL D1 D0 Clock Data or F 2F signaling also provides tri state LED control and buzzer control one wire LED mode only Two Form C contact relay outputs may be used for door strike control or alarm signaling The relay contacts are rated at 2 A 30 Vdc dry contact configuration Two inputs are provided that may be used for monitoring the door contact exit push button or alarm contact Input circuits can ...

Страница 2: ...2 GND Auxiliary Power Output Ground TB4 3 VIN Input Power 12 Vdc from local power supply TB4 4 GND Input Power Ground TB5 1 NO Relay K1 Normally Open Contact TB5 2 1 C Relay K1 Common Contact TB5 3 NC Relay K1 Normally Closed Contact TB5 4 NO Relay K2 Normally Open Contact TB5 5 2 C Relay K2 Common Contact TB5 6 NC Relay K2 Normally Closed Contact Note 1 Terms A B are from the RS 485 standard Jump...

Страница 3: ...unication address 0 Alternate Host Port Disabled 4 Bulk Erase Configuration Memory The bulk erase function can be used for the following purposes Erase all configuration and cardholder database sanitize board Update OEM default parameters after OEM code has been changed Recover from database corruption causing LP1501 board to continuously reboot If clearing the memory does not correct the initiali...

Страница 4: ...ote serial I O devices using MSP1 protocol or up to two OSDP devices If two OSDP devices are used reader port 2 will not support a third reader If only one OSDP device is configured then reader port 2 is available for a second reader The maximum cable length is 2000 ft 610 m Do not terminate any RS 485 devices connected to reader port 1 When powering remote device s from the LP1501 be cautious not...

Страница 5: ...AL I O MODULE MR16in MR16out FOR EXAMPLE MR62e MR50 MR52 GND GND 12 Vdc TR TR MR62e FOR EXAMPLE MR50 MR16out MR16in MR52 GND TR 12 Vdc GND TR TR TR FIRST READER PORT REFER TO THE APPROPRIATE REMOTE SERIAL I O DEVICE INSTALLATION MANUAL FOR ADDRESS AND BAUD RATE SETTINGS DO NOT TERMINATE ANY OF THE DEVICES ON THE RS 485 MULTI DROP COMMUNICATION BUS EACH REMOTE SERIAL I O DEVICE MUST BE CONFIGURED W...

Страница 6: ... a Common pole C a Normally Open pole NO and a Normally Closed pole NC When you are controlling the delivery of power to the door strike the Normally Open and Common poles are used When momentarily removing power to unlock the door as with a mag lock the Normally Closed and Common poles are used Check with local building codes for proper egress door installation Door lock mechanisms can generate E...

Страница 7: ...ne 80 ON 2 Host Communication Activity 3 Readers combined Clock Data or D1 D0 Mode Flashes when Data is Received Either Input RS 485 Mode Flashes when Transmitting Data F 2F Mode Flashes when Data Acknowledgment is Received 4 Input IN1 Status OFF Inactive ON Active Flash Fault See Note 1 5 Input IN2 Status OFF Inactive ON Active Flash Fault See Note 1 6 Cabinet Tamper 7 Reserved for Future Use D9 ...

Страница 8: ...nication Ethernet 10 BaseT 100Base TX and Micro USB port 2 0 with optional adapter pluggable model USB2 OTGE100 Inputs Two unsupervised supervised Programmable End of Line resistors 1k 1k ohm 1 watt standard One unsupervised input dedicated for cabinet tamper Outputs Two relays Form C contacts 2 A 30 Vdc resistive Reader Interface Power 12 Vdc 10 PoE PoE or local power supply 300 mA maximum Data I...

Страница 9: ...Levels Feature Level Standby Power I Endurance IV Line Security I Destructive Attack I These specifications are subject to change without notice 14 Additional Mounting Information Sources for the optional items shown below 3 gang stainless steel blank cover Available from Leviton part number 84033 40 Graybar part number 88158404 Magnetic switch set G R I part number 505 FIELD WIRING LP1501 WITH IN...

Страница 10: ...ied warranties and expressly excludes and disclaims all implied warranties of merchantability or fitness for a particular purpose Returns must be accompanied by a Return Material Authorization RMA number obtained from customer service and prepaid postage and insurance Liability The Interface should only be used to control exits from areas where an alternative method for exit is available This prod...

Отзывы: