Typical D1/D0 or Clock/Data Reader 

Typical 2-wire RS-485 Device

 

 

 
 

* Inputs on supervised F/2F readers may be unsupervised or supervised (supervised shown). 

 

 

Typical Unsupervised F/2F Reader 

Typical Supervised F/2F Reader 

 

Jumper D1 to LED on supervised F/2F readers 

 

8.   Input Circuit Wiring: 

Typically, these inputs are used to monitor door position, request to exit, or alarm contacts.  Input circuits 
can be configured as unsupervised or supervised.  When unsupervised, reporting consists of only the open 
or closed states.  When configured as supervised, the input circuit will report not only open and closed, but 
also open circuit, shorted, grounded*, and foreign voltage*.  A supervised input circuit requires two resistors 
be added to the circuit to facilitate proper reporting.  The standard supervised circuit requires 1k ohm, 1% 
resistors and should be located as close to the sensor as possible.  Custom end of line (EOL) resistances 
may be configured via the host software. 

* Grounded and foreign voltage states are not a requirement of UL 294 and therefore not verified by UL 

The input circuit wiring configurations shown are supported but may not be typical: 

 

1

TB8 or TB9

VO

LED

BZR

GND

D1/CLK/TR+

D0/DAT/TR-

VO

LED

BZR

D1/CLK/TR+

D0/DAT/TR-

GND

1

TB8 or TB9

VO

LED
BZR

D1/CLK/TR+

D0/DAT/TR-

GND

+12 Vdc

D1

GROUND

DO (GREEN LED)

F/2F Reader

1

TB8 or TB9

1

VO

LED
BZR

D1/CLK/TR+

D0/DAT/TR-

GND

+12 Vdc

D1

GROUND

DO (GREEN LED)

F/2F Reader

NORMALLY CLOSED CONTACT *

DOOR MONITOR SWITCH

REQUEST TO EXIT SWITCH
NORMALLY OPEN CONTACT *

1K,1%

1K,1%

1K,1%

1K,1%

TB8 or TB9

1K,1%

1K,1%

1K,1%

1K,1%

IN4     IN3 

    IN2   

 IN
1

Standard Supervised Circuit,
Normally Closed Contact

Standard Supervised Circuit,

Normally Open Contact

Unsupervised Circuit,
Normally Open Contact

Unsupervised Circuit,
Normally Closed Contact

Terminal Blocks

TB4 through TB7

Содержание EP1502

Страница 1: ...d that may be used for monitoring the door contacts exit push buttons and alarm contacts Input circuits may be configured as unsupervised or supervised The EP1502 requires 12 to 24 Vdc for power 2 EP1...

Страница 2: ...lly Open Contact TB5 2 IN4 TB11 2 C Common TB5 3 Input 3 IN3 TB11 3 NC Normally Closed Contact TB5 4 IN3 TB11 4 Out 4 NO Normally Open Contact TB6 1 Input 6 IN6 TB11 5 C Common TB6 2 IN6 TB11 6 NC Nor...

Страница 3: ...wing purposes Erase all configuration and cardholder database sanitize board Update OEM default parameters after OEM code has been changed Recover from database corruption causing EP1502 board to cont...

Страница 4: ...ort supports a reader with TTL D1 D0 Clock Data F 2F or 2 wire RS 485 signaling Power to the readers is selectable 12 Vdc VIN must be greater than 20 Vdc or power is passed through PASS from the input...

Страница 5: ...e standard supervised circuit requires 1k ohm 1 resistors and should be located as close to the sensor as possible Custom end of line EOL resistances may be configured via the host software Grounded a...

Страница 6: ...tallation the user accounts to the web configuration page should be created with secure passwords and that all DIP switches are in the off position for the normal operating mode The EP1502 is shipped...

Страница 7: ...le See Note 1 IN3 Input IN3 Status OFF Inactive ON Active Flash Trouble See Note 1 IN4 Input IN4 Status OFF Inactive ON Active Flash Trouble See Note 1 IN5 Input IN5 Status OFF Inactive ON Active Flas...

Страница 8: ...ee from defects in material and workmanship under normal use and service with proper maintenance for one year from the date of factory shipment Mercury Security assumes no responsibility for products...

Отзывы: