2
Strider M72
ME-PM-M72
Data Update Rate
1 second nominal
Input-Voltage
VT Primary
100~500000V ac
Un
230 V L-N
Measured Voltage with Over-range and
Crest Factor
100 to 480Vac L-L
100 to 276Vac L-N
Permanent Overload
490V L-L
280V L-N
Impedance
1M Ω
Frequency Range
45~66Hz
Input- Current
CT Rating
Primary
1~9999A
Secondary
333mV
Measured current with Over-range
and Crest Factor
5mA~6A
Withstand
Continuous 8A 120A for 0.5Seconds
Impedance
<1 mΩ
Frequency Range
45~66Hz
Burden
<0.036VA at 6A
Auxiliary Power Supply
Operating Range
65~480V AC / 80~660V DC
Power Consumption
< 7VA/3.5W.
Frequency
45 to 65 Hz
Weight
250g
IP Degree of Protection (IEC 60529)
IP51 front display
Dimensions (WxHxD)
96x96x70.3
Mounting Position
Vertical
Mechanical characteristics
Panel Thickness
1~5mm
Material of meter case
Self-extinguishing UL 94 V-0
Mechanical environment
M1
Operating Temperature
-25 to 55°C
Storage Temperature
-40 to 70°C
Humidity Rating
<95% RH at 50 °C (non-condensing)
Pollution Degree
2