OPERATION AND MAINTENANCE MANUAL mcr LAM vents
Page 5 of 20
mcr LAM louvered vents come with the following types of actuators:
• electrical, 24 V DC,
• pneumatic – powered by CO
2
(smoke exhaust function) or by compressed air (daily
ventilation function),
• electrical 230V AC (daily ventilation only).
Only pneumatically operated mcr LAM smoke vents are equipped with flow control valves with
thermal release valve (including thermal fuse).
The louvered vents may be operated locally - manually or automatically by thermal release
valves (in the case od smoke vents) or remotely by an MCR smoke control panel or fire alarm
control panel.
Figure 1. mcr LAM louvered vent
4
1
2
3
5
4
Shipment and delivery
mcr LAM louvered vents are supplied factory assembled, except for additional external
flashings, higher base assembles, etc. which, if required, come separately. The roof curbs, i.e.
additional base assemblies, always come separately. The reason is to protect the different
components from damage during transport and avoid road safety hazards. The vents can be
unloaded manually or by means of universal loading equipment in the presence of a person
authorised by the manufacturer.
1.
mcr LAM vent base
2.
Louver blades
3.
Wind deflectors
4.
Roof curb
5.
Actuators