mcr FID 240 

single-blade fire dampers 

“MERCOR” SA 

– The company reserves the right to modify and change the document. Version FID 240 21.07.29.1 

15/19 

Auxiliary circuit 
breaker: 

2 x SPDT 6A (3) max 250 V AC 

2 x SPDT 6A (3) max 250 V AC 

- activation position 

5°, 80° 

5°, 80° 

Torque: 

  

  

- motor 

18 Nm 

18 Nm 

- spring 

12 Nm 

12 Nm 

Movement time: (90°) 

  

  

- motor 

150 s 

150 s 

- return spring 

20s 

20s 

Ambient temperature 

- 20 ...+50°C 

- 20 ...+50°C 

 

 

Connection diagram for the EXBF actuators 

 

Caution:  

For  proper  operation  of  a  device  equipped  with  electrical  actuators,  it  is  recommended  that  the  rated 
voltage housed tolerance of 24V±10% or 230V±10%. Power supply devices other than listed above may 
cause malfunction and will not be covered by the warranty conditions.  

 
RST/KW1 trigger control gear 

The RST/KW1/S version has the limit switches installed in the gear itself. The electrical connections shall 
be  made  by  connecting  the  properly  labelled  conductors  to  the  electrical  system.  A  fusible  trigger  is 
installed in the gear. The dampers with the  RST/KW1/230I, RST/KW1/230P mechanisms, are supplied 
with the RST/KW1/24... triggering and control mechanism, together with the 230/24V transformer module 
type MP230/24. For the trigger and control mechanism of the "impulse" type  damper,  adequate power 
must be provided to ensure that the control signal is supplied to the device in the event of fire.

 

 

 

RST/KW1/S

 

RST/KW1/24I

 

RST/KW1/24P

 

RST/KW1/24I 

+MP230/24

 

RST/KW1/24I

 

+MP230/24

 

Supply voltage 

24 V – 48 V 

DC 

24 V – 48 V 

DC 

230V AC 

230V AC 

Power consumption 

3.5 W 

1.6 W 

4.5 W 

2.5 W 

Holding force 

12 daN 

12 daN 

12 daN 

12 daN 

Thermal trigger trip 

point 

72°C +-2°C 

WK1d / WK2d limit 

switch 

NO/NC (switching contact) 

5A, 230V AC 

Switch trigger 

3°, 87° – tolerance: +/- 2°

 

Limit switch operating 

temperature 

-25 ...+85°C 

Electrical connection 

- release: cable 0.6 m, 2x0.5 mm

2

 

- limit switch: cable 0.6 m, 6x0.5 mm

2

 

EX zone

 

EEx-e rated installation box

 

 

Thermal 
trigger

 

Содержание mcr FID 240

Страница 1: ...Ul Grzegorza z Sanoka 2 80 408 Gdańsk tel 0 58 341 42 45 tel fax 48 58 341 39 85 OPERATION AND MAINTENANCE MANUAL OMM Fire damper type mcr FID 240 Version FID S 240 21 07 29 1 FIRE VENTILATION SYSTEMS ...

Страница 2: ... INSTALLATION 7 6 1 PRE ASSEMBLY INSPECTION 7 6 2 INSTALLATION OPENING 7 6 3 EMBEDDING FIXING THE DAMPER 8 6 4 ELECTRICAL CONNECTIONS 9 7 TRANSPORT STORAGE CONDITIONS 17 8 MAINTENANCE AND SERVICING 17 9 WARRANTY TERMS CONDITIONS 18 Technical Manual designations Option available Option unavailable CAUTION All previous issues of this Technical Manual expire on the date of issue hereof The Technical ...

Страница 3: ...the case of cut off and transfer fire dampers the device is equipped with a thermal release containing one time temperature fuses During normal operation the above mentioned element should be protected against the affect of the permissible temperature Tmax see the table below When it is exceeded the temperature fuses may operate which is a normal operation and is not covered by the guarantee or wa...

Страница 4: ...tilation systems mcr FID 240 V cut off fire dampers for mixed fire ventilation systems mcr FID 240 V M transfer dampers mcr FID 240 T relief dampers mcr FID 240 G Caution Cut off fire dampers for fire ventilation systems the mcr FID 240 V and fire dampers for mixed fire ventilation systems the mcr FID 240 V M have one declaration of performance in accordance with the requirements of law The marker...

Страница 5: ...tuator in the right manner remotely by tripping the electromagnetic release and a spring as a result of applying the voltage cut off fire dampers for mixed fire ventilation systems mcr FID 240 V M In normal operation the dampers are closed or open depending on the function carried out The dampers are opened closed to the safety position as follows remotely by tripping the electrical axial actuator...

Страница 6: ... G BLE 24 ST S V V M T G BFL 24 T ST S V V M T G EXBF 230 S V V M T G BFN 230 T S V V M T G EXBF 24 S V V M T G BFN 24 T ST S V V M T G BF 230 TN S V V M T G BF 24 TN ST S V V M T G BF 24 TN TL S V V M T G BEE 230 S V V M T G BEE 24 ST S V V M T G BEN 230 S V V M T G BEN 24 ST S V V M T G MF 230 T S V V M T G MF 24 T S V V M T G MLF 230 T S V V M T G MLF 24 T S V V M T G Spring gear RST S V V M T ...

Страница 7: ...e damper sets The mcr FID 240 fire dampers may also be installed in partitions with a lower class of fire resistance In this case the damper fire resistance is equal to the partition fire resistance if the smoke tightness is met When installing the fire damper in a wall the thickness of which is below the required minimum increase the thickness at the installation location e g by adding an extra s...

Страница 8: ...sterboard bands around the damper body The moving isolation partition must remain closed throughout the installation After installation remove the supports and reopen and close the damper to check if it works properly In order to ensure the fire resistance of the fire separation element it is mandatory to keep the embedding envelope boundary the damper isolation partition rotation axis must be wit...

Страница 9: ...ire resistance for the applied method of assembly 6 4 ELECTRICAL CONNECTIONS After the damper has been properly installed and embedded if it has control elements or other elements that require electrical installation connect the cables of this installation to the damper Connection diagrams and basic electrical data of the release and control mechanisms supplied with the mcr FID 240 fire dampers ar...

Страница 10: ... 0 90 motor 120 s 120 s return spring 16 s 16 s Operating temperature range 30 50 C 30 50 C Sound pressure level motor max 45 dB A max 45 dB A spring 63 dB A 63 dB A Technical specifications BE24 BE24 ST BE230 BLE24 BLE24 ST BLE230 Power supply AC 24V 50 60Hz DC 24 V AC 220 240V 50 60 Hz AC 24V 50 60Hz DC 24V AC 220 240V 50 60 Hz Power demand for spring tensioning 12 W 8 W 7 5 W 5 W for spring hol...

Страница 11: ...250V 2xSPDT 3A AC 250V activation position degrees 5 80 5 80 5 80 5 80 Torque motor 25 Nm 25 Nm 15 Nm 15 Nm Cable connection motor L 0 9 m 3x0 75 mm2 3x0 75 mm2 3x0 75 mm2 3x0 75 mm2 auxiliary circuit breaker 6x0 75 mm2 6x0 75 mm2 6x0 75 mm2 6x0 75 mm2 Movement time 0 90 60s 60 s 30 s 30 s motor Operating temperature range 30 55 C 30 55 C 30 55 C 30 55 C Sound pressure level motor max 58 dB A max ...

Страница 12: ...3 dB A 62 dB A max 55 dB A 67 dB A max 55 dB A 67 dB A Technical specifications MLF 24T MLF 230T Power supply AC 24V 50 60Hz DC 24 V AC 220 240V 50 60 Hz Power demand for spring tensioning 5 W 5 W for spring holding 2 5 W 3 W Sizing apparent power 7 VA 7 VA Appliance class III II Ingress protection rating IP 54 IP 54 Auxiliary circuit breaker 2xSPDT 6 1 5 A AC 250V 2xSPDT 6 1 5 A AC 250V activatio...

Страница 13: ...ght to modify and change the document Version FID 240 21 07 29 1 13 19 Connection diagram for the BF24 Tand BF230 T actuators Connection diagram for the BFL24 T BFL230 T BFN24 T BFN230 T BF24 TN and BF230 TN actuators Connection diagram for the MLF 24T MLF 230T MF 24T MF 230T ...

Страница 14: ...cation of the limit switches for all types of actuators is shown for the position without voltage For proper operation of a device equipped with electrical actuators it is recommended that the rated voltage housed tolerance of 24V 10 or 230V 10 Power supply devices other than listed above may cause malfunction and will not be covered by the warranty conditions EXBF actuators Technical specificatio...

Страница 15: ...ections shall be made by connecting the properly labelled conductors to the electrical system A fusible trigger is installed in the gear The dampers with the RST KW1 230I RST KW1 230P mechanisms are supplied with the RST KW1 24 triggering and control mechanism together with the 230 24V transformer module type MP230 24 For the trigger and control mechanism of the impulse type damper adequate power ...

Страница 16: ...ice equipped with electrical actuators it is recommended that the rated voltage housed tolerance of 24V 2 or 230V 2 Power supply devices other than listed above may cause malfunction and will not be covered by the warranty conditions RST trigger control gear In the RST version the limit switches are independent units installed inside the fire damper casing The fusible release is located on the dam...

Страница 17: ...vide protection against external weather conditions In the case dampers are stored on the ground place them on protection pads in order to protect them against damage Storage should take place in rooms where there is no access to dust gases caustic vapors and other aggressive chemical vapors that can destroy insulating elements and structural elements the dampers are not affected by direct sunligh...

Страница 18: ...sing from causes present in the equipment at the date of sale 7 Defects caused by improper operation or otherwise as listed in Item 10 herein the buyer warranty beneficiary will be charged with the costs of their removal 8 Condition for rectifying defects is that the applicant makes the site localisation where devices are installed available in particular ensuring the lift in the case of devices m...

Страница 19: ...rating plate and or warranty seals 11 The buyer warranty rights holder is required to operate the equipment properly and carry out technical inspection and maintenance in accordance with the section MAINTENANCE AND SERVICING in the following Operating and Maintenance Manual 12 This warranty shall be made immediately void and null if The buyer warranty rights holder modifies the product design with...

Отзывы: