background image

CAUTION

:  Do  not  exceed  specified  supply  voltage  ratings.

Permanent damage not covered by warranty will result. This

device is not designed for 120 or 240 volt AC operation. Use

only on 10 to 28 VDC. 

INSTALLATION

1.  Location

:  Select  a  location  where  the  temperature  of  the  transducer  will  be

between -4 and 176°F (-20 to 80°C) for ETFE cable or -4 and 149°F (-20 to 65°C)

for    polyurethane  cable.  Distance  from  the  receiver  is  limited  only  by  total  loop

resistance.

2. Position

: The transducer is not position sensitive. However all standard models

are  originally  calibrated  with  the  unit  in  a  position  with  the  pressure  connection

downward.  Although  they  can  be  used  at  other  an  gles,  for  best  accuracy  it  is

recommended that units be installed in the position calibrated at the factory.

3.  Mounting

:  The  transducer  can  be  mounted  via  several  methods.  It  can  be

suspended from the electrical cable, it can be placed resting on the bottom of the

tank in either horizontal or vertical orientation, or it can be attached to a pipe or

hang wire by the 1/2˝ NPT male connection on the top of the housing.

4. Electrical Connections

Wire Length

- The maximum length of wire connecting the transducer and receiver

is a function of wire size and receiver resistance. Wiring should not contribute more

than 10% of the receiver resistance to total loop resistance. For extremely long runs

(over 1000 feet), choose receivers with higher resistance to minimize the size and

cost of connecting leads. Where wiring length is under 100 feet, wire as small as

22 AWG can be used.

5. Wiring

An external power supply delivering 10-28 VDC with minimum current capability of

40 mA DC (per transducer) is required to power the control loop. See Fig. A for

connection of the power supply, transducer and receiver. The range of appropriate

receiver  load  resistance  (rL)  for  the  DC  power  supply  voltage  available  is

expressed by the formula:

rL max = Vps – 10V

20 mA DC

Shielded cable is recommended for control loop wiring. 

Black wire is negative (-) and red wire is positive (+).

MAINTENANCE

After final installation of the pressure transducer and its companion receiver, no

routine  maintenance  is  required.  A  periodic  check  of  system  calibration  is

suggested. The Series SBLTX transducer are not field repairable and should be

returned  if  repair  is  needed  (field  repair  should  not  be  attempted  and  may  void

warranty). Be sure to include a brief description of the problem plus any relevant

application notes. Contact customer service to receive a return goods authorization

number before shipping. 

POWER
SUPPLY
10-28 VDC

-

RECEIVER

BLACK

RED

PRESSURE

TRANSDUCER

mA

   

   

Fig. A

Fig. B