Example 3. Multiuser System
A landlord has a block of four small industrial units to let.
Each unit is fitted with a personnel door and a large
vehicle door. At the back of the unit is a small room that
can be used as an office. At the end of the block of units
is a service room.
The landlord wishes to fit each unit with its own alarm
system, operated solely by the tenant. In each unit the
installer fits door contacts on both external doors, a
panic alarm in the office, a smoke detector in the
ceiling and a PIR to cover most of the main area of the
unit. A keypad next to the personnel door allows the
tenant to set and unset the system. A bell/strobe unit on
the outside of the unit provides an alarm. The installer
connects all the devices in a unit to a single xnode,
fitted inside the unit and connected by cable to the
service room.
In the service room the installer fits the control panel,
another keypad (for programming the system) and a
PIR and door contact to protect the service room.
During programming the installer assigns each unit to
an individual ward, A to D, and the service room to Ward
E. Note how the zone numbering has gaps in it. This is
because each xnode has only five detectors.
See also “Ward Sounder Control” on page 6.
4
TS2500 Hints and Tips
RK
C
P
CP
P
C
PA
Fr
Key:
Passive Infra-Red Detector
Magnetic Contact
Panic Alarm
Smoke Detector
RK
Remote Keypad
CP
Control Panel
XN
Xnode
XN
Bell
Bell
Bell/Strobe
Bell
RK
C
C
P
XN
PA
Fr
Bell
RK
C
C
P
XN
PA
Fr
Bell
RK
C
C
P
XN
PA
Fr
Bell
RK
C
C
P
XN
PA
Fr
Ward A
Ward B
Ward C
Ward D
Ward E
1001
1009
1017
1025
1033
1004
1012
1020
1028
1034
1005
1013
1021
1029
1003
1011
1019
1027
1002
1010
1018
1026
Assign circuit types.
Assign circuit attributes.
Allocate zones to wards.
Program system timers.
1 4
Program setting modes.
Program network equipment
to wards.
Program other equipment
to wards.
Assign detectors in each unit to
respective Ward. Assign detectors in
service room to Ward E.
Each ward must have its own exit and
entry delay time. In the example, wards
A to D have entry and exit times of
60s.
Each ward must have its own setting
mode. All wards are programed as
final exit.
Make sure that eac xnode is assigned
to its own ward.
Assign keypads to respective wards.
Make sure that tampers are assigned
to the correct nodes.
In the example the panel and service
room bellbox tamper are assigned
to ward E.
ENT
ENT
1 5
ENT
ENT
1 6
ENT
ENT
4 2
ENT
ENT
4 3
ENT
ENT
Enter Engineer's
Passcode
1234
Return to Day Mode.