85-03-01205
ML-SERIES FIREPLACE
Page
48
3.4.8
Gas Input Rate Verification
3.4.8.1
Natural Gas Input Rate Verification
1. Verify main orifice size. The main orifice body has the orifice hole size stamped on it. NG orifice size shall be #33
(ML39), 1/8
”
(ML47, ML54, or ML60), and #30F #43R (ML72) for 0-2000 ft and #34 (ML39), #31 (ML47), 1/8
”
(ML54 and ML60), and #30F #43R (ML72) for 2000-5000ft.
2. Verify that the Manifold Gas Pressure is within 3.5" WC +/-
1/8". Once setup, read the main home gas supply meter
reading.
3. Write the initial reading here >> initial gas meter reading
Turn off all other appliances and their pilot flame in the home.
4. Run this appliance for a period of 30 minutes on maximum flame size. Turn off main burner and pilot
flame. Read the main home gas supply meter reading after the 30 minutes of burn time.
5. Write the reading here >> final gas meter reading
Calculate the following:
6. FINAL GAS METER READING - INITIAL GAS METER READING...Subtract initial gas meter from final gas meter
reading. This will yield the number of Therms used during the 30-minute burn time.
7. Multiply the result in Item #6 by 100,000.
8. Multiply the result in Item #7 by 2. Write down the result here >>
9. The result in item #8 shall be at least the maximum input rate: 34,250 Btu/Hr (ML39), 41,000 Btu/Hr (ML47, ML54,
or ML60), and 60,000 (ML72) for all altitudes.
3.4.8.2
LPG Input Rate Verification
Verify main orifice size. The main orifice body has the orifice hole size stamped on it. LPG orifice size shall be #50 (ML39),
#48 (ML47), #49 (ML54 and ML60), and #46F #54R (ML72) for 0-2000 ft and #51 (ML39), #49 (ML47, ML54, or ML60),
and #46F #54R (ML72) for 2000-5000ft.
Verify that the manifold gas pressure is within 10.0" WC +/- 1/8".
3.4.9
High Altitude De-Rating
If you are de-rating this appliance at a high altitude, attach the High-Altitude De-Rating Label, supplied in the
Owner’s
Manual Packet, to the back surface of the listing label plate located in the air gap on the side of the Fireplace. If you
are also converting the Fireplace for LP Gas attach the labels included with the conversion kit to the same surface.
Prior to attaching the label, fill in all the information that is requested on the label.
For installations from 610-1370 meters (2000-5000 ft.) the orifice sizes (DMS) for Natural Gas are
#34 (ML39), #31 (ML47),
1/8
”
(ML54 and ML60), and #30F #43R (ML72).
Propane Gas is
#51 (ML39), #49 (ML47, ML54, or ML60), and #46F #54R (ML72)
.
See data plate for additional information. For high altitude installations consult the local gas distributor or the authority
having jurisdiction for proper rating methods. If the installer must convert the unit to adjust for varying altitudes, the
information sticker must be filled out by the installer and adhered to the appliance at the time of conversion."
This appliance has been converted for use at an altitude of:
Orifice size:
Manifold Pressure:
Input (Btu/h):
Fuel Type:
Date of conversion:
Converted by:
Cet appreeil a été converti au ____
Injecteur ________
Pression à la tubulure d'alimentation _____________
Déoit calorifique ______________
Содержание ML39- AA-11-04391
Страница 2: ...85 03 01205 ML SERIES FIREPLACE HOMEOWNER NOTES...
Страница 16: ...85 03 01205 ML SERIES FIREPLACE Page 16 Figure 3 10 Figure 3 9...
Страница 87: ...85 03 01205 ML SERIES FIREPLACE Page 87 ML72 Gas Train Assembly Parts...
Страница 94: ......
Страница 95: ...Johnson Gas Appliance Company 520 E Avenue NW Cedar Rapids Iowa 52405 Mendota Warranty Registration...