85-03-01120
M27
Page
37
Side by Side installation of two Vent Caps
When two or more vertical vent caps are located within proximity of one another, it is required that a galvanized steel 18-gauge
or heavier barrier wall be installed between the two vent caps to eliminate recirculation of exhaust gases from one cap to
another.
The galvanized steel barrier shall be 6" taller than the highest point of the vent caps and shall be 3" wider past the outer edges of
the vent caps.
If two gravity direct vent system gas appliances are terminated next to each other, the minimum required distance between the
vertical center line of the vent caps is
18”
to prevent recirculation of exhaust from one vent cap outlet into the air intake of
another vent cap.
If a wood burning flue opening is adjacent to a gravity direct vent system gas appliance vent cap and the distance between
vertical center lines of the two terminations is less than
36”
, we recommend a metal divider plate be installed to prevent wood
burning exhaust from entering the gas appliance air intake path. Alternatively, you may also vertically extend the wood burning
flue liner up 24” higher than the top surface of the gas appliance vent cap.
Figure 3-23 Side by Side Vent Caps
Содержание CHELSEA M-27
Страница 2: ...85 03 01120 M27 Page 2 HOMEOWNER NOTES ...
Страница 16: ...85 03 01120 M27 Page 16 Figure 3 8 Figure 3 7 ...
Страница 19: ...85 03 01120 M27 Page 19 Fireplace Dimensions and Clearances Figure 3 10 Overall Fireplace Dimensions ...
Страница 22: ...85 03 01120 M27 Page 22 Clearance from Appliance Outer Surfaces Figure 3 14 CLEARANCES TO APPLIANCE BODY ...
Страница 35: ...85 03 01120 M27 Page 35 Approved Vent Systems ...
Страница 62: ...85 03 01120 M27 Page 62 ...
Страница 64: ...85 03 01120 M27 Page 64 ...
Страница 65: ...85 03 01120 M27 Page 65 VERTICAL THROUGH THE ROOF VENTING USING THREE 900 ELBOWS ...
Страница 69: ...85 03 01120 M27 Page 69 ...
Страница 70: ...85 03 01120 M27 Page 70 ...
Страница 71: ...85 03 01120 M27 Page 71 ...
Страница 72: ...85 03 01120 M27 Page 72 ...
Страница 73: ...85 03 01120 M27 Page 73 ...
Страница 74: ...85 03 01120 M27 Page 74 ...
Страница 103: ......
Страница 104: ...Johnson Gas Appliance Company 520 E Avenue NW Cedar Rapids Iowa 52405 Mendota Warranty Registration ...