85-03-01154
FV36 DÉCOR
Page
83
MAINTENANCE INFORMATION
5.1
REQUIRED PERIODIC INSPECTIONS
1.
Check to verify that the vent system and vent cap are open and free of blockage.
2.
Have qualified service person check the operation of the pilot light. Pilot light must light within the first five to eight
seconds of ignitor sparks initiation. If it takes more ten seconds to ignite the pilot flame, check pilot spark rod position and
ignitor wires for pinched areas or damaged areas.
3.
Pilot rectification time must be checked. Pilot flame should rectify the
ignition system within five seconds of pilot flame ignition and sparking at
pilot must stop with five seconds. If pilot flame ignites but sparking
continues at pilot hood after five seconds, it indicates that pilot flame
sensor is dirty. Clean pilot flame sensor using emery cloth and retry. If
problem persists, check flame sensor lead wire for damage or grounding
problems and correct.
4.
Periodic visual check of pilot flames is required. Pilot Flame must overlap
Flame Sensor and burner ignition ports always. Especially for LPG
applications, always verify visible pilot flame length is at least 1" long,
minimum.
5.
Cycle the burner to make certain burner ignition is prompt and flame
propagation along burner length is quick and smooth. If flame
propagation is delayed, remove obstructing debris, vacuum burner ports
and retry.
6.
Periodic visual check of rear and front burner flames pattern is required.
5.2
CLEANING VIEWING GLASS
WARNING: Do not clean when glass is hot.
The viewing glass should be cleaned periodically. Exterior glass surface may be cleaned with cleaner as desired. To clean
Interior glass surface, remove glass frame assembly.
. U
se Kel Kem “polish plus" (part # 65
-06-
00455) or comparable product to clean glass interior surface. Do not use oven cleaner or abrasive cleaners to clean glass.
5.3
REQUIRED ANNUAL MAINTENANCE
See
Chapter 4.11.4 What maintenance is required?
In addition to the “Required Periodic Inspections”, the
following procedures must be performed each year by
a qualified installer, service agency or the gas supplier . Any adjustments to burner, pilot or logs must be
done by a qualified installer, service agency, or the gas supplier .
Clean all lint and dust build-up around the control and blowers. Inspect the condition of any wiring under the burner for melting
or damage. Clean flame sensor rod/hook using emery cloth. Vacuum all burner ports and pilot assembly.
Remove logs & coals and clean away any foreign matter (lint, Carbon, etc.) on the burner and logs. Be sure the burner ports are
"open". Clean the pilot and under side of the logs for any Carbon deposits.
NOTE: Logs should be visually checked for Carbon "build -up". If heavy carbon deposits are visible on logs,
unit should be turned off and a qualified installer, service agency, or the gas supplier should be contacted .
Be sure logs are re-installed per instructions.
Check glass gasket seal. Visually inspect glass gasket, especially at the corners of the glass piece. Glass gasket is installed as a 4-
piece assembly. Check joints between the gasket pieces at the corners. They should butt against each other to create a seal. Gaps
between gasket pieces can cause exhaust leaks and lead to acrid smell concerns.
Figure 5-1 Minimum Pilot Flame Length
1" MIN.
1" MIN.
Содержание AA-11-04109
Страница 2: ...85 03 01154 FV36 D COR...
Страница 16: ...85 03 01154 FV36 D COR Page 16 Figure 3 11 Figure 3 10...
Страница 24: ...85 03 01154 FV36 D COR Page 24 Clearance from Appliance Side Walls Figure 3 17 CLEARANCE TO BODY...
Страница 87: ...85 03 01154 FV36 D COR Page 87 Gas Train Assembly Parts Figure 5 5 Gas Train Assembly Parts...
Страница 88: ...85 03 01154 FV36 D COR Page 88 Burner Figure 5 6 Burner...
Страница 95: ......
Страница 96: ...Johnson Gas Appliance Company 520 E Avenue NW Cedar Rapids Iowa 52405 Mendota Warranty Registration...