background image

Installation Manual: MEMC Silvantis 60 cell PV Modules

6 of 15

© Copyright 2012 MEMC Electronic Material

REAR VIEW

FRONT VIEW

A

PErPEndICuLAr MounTIng  

(CASES 1 & 2)

Structural rails running perpendicular to 
the length of the module should be fixed 
via bolts or clamps at the mounting holes 
between each long side frame, or at the 
holes on each short end frame. 

noTE: All modules are rated for a 
maximum rear load of 2400 Pa and a 
maximum front load of 5400 Pa  when 
fixed to the side frames mounting holes 
for CASE 1 or a front load of 2400 Pa 
when fixed to the end frames mounting 
holes for CASE 2. 

PArALLEL MounTIng (CASE 3)

Structural rails running parallel to the length 
of the module should be fixed via bolts or 
clamps onLy at the mounting holes on 
each long side frame. 

noTE: All modules are rated for a 
maximum rear load of 2400 Pa and a 
maximum front load of 5400 Pa when 
fixed to the mounting holes on the long 
side frames only. 
Structural rails running parallel to the 
length of the module should nEvEr be 
fixed to the end frames.

Maximum  
rear Load: 

2400 Pa or 50 psi

Maximum  
front Load:

5400 Pa or 113 psi

Maximum  
rear Load: 

2400 Pa or 50 psi

Maximum  
front Load:

5400 Pa or 113 psi

Maximum  
rear Load:

2400 Pa or 50 psi

Maximum  
front Load:

5400 Pa or 113 psi

REAR VIEW

FRONT VIEW

A

REAR VIEW

FRONT VIEW

B

BoLT MounT 

 LoCATIonS

CLAMP MounT 

LoCATIonS

MounTIng ConfIgurATIonS

LoAd PArAMETErS

C

ASE

 1

C

ASE

 2

C

ASE

 3

Module Color Code:       Mounting hole Location   

  Module rail  

     Clamp Mount range

Clamp mount 

allowable range

Clamp mount 

allowable range  

A – 382 mm  
B – 248 mm 

 Clamp mount allowable range:  

Clamp mount 

allowable range  

4.2A MounTIng ConfIgurATIonS uSIng BoLT MounT or CLAMP MounT oPTIonS

Содержание SunEdison MEMC-M235AMA

Страница 1: ...A MEMC M240AMA MEMC M245AMA MEMC M250AMA MEMC M255AMA MEMC M240LMA MEMC M250LMA MEMC M260LMA MEMC M240AMC MEMC M245AMC MEMC M250AMC MEMC M255AMC MEMC M260AMC MEMC M240LMC MEMC M250LMC MEMC M260LMC Ins...

Страница 2: ...tallation using shared rails M240 250 260LMA and M240 250 260LMC 7 4 5 Mechanical Installation Warnings 8 5 0 Electrical Installation 8 5 1 Planning and Design 8 5 2 Module Wiring 8 5 3 Grounding 9 5...

Страница 3: ...vantis Photovoltaic modules consist of a series of electrically interconnected crystalline silicon solar cells that are sealed within a laminated sheet of tempered glass superstrate and EVA back sheet...

Страница 4: ...cing which may result in burns fires or other problems Follow industry best practices when commissioning trouble shooting disconnecting or connecting a PV system Trouble shooting should include planni...

Страница 5: ...ations For mounting locations for clamps or bolt for specified load please refer to Table on page 6 Each module should be mounted using four bolts through the mounting holes on the rear side of the mo...

Страница 6: ...oles on each long side frame NOTE All modules are rated for a maximum rear load of 2400 Pa and a maximum front load of 5400 Pa when fixed to the mounting holes on the long side frames only Structural...

Страница 7: ...260LMC SPECIFIC Toe in Modules using Corner Cap Feature System Overview Installation Step Illustration Toeing module into rail hook Module clip attachment Step 1 Place the bottom of the module on the...

Страница 8: ...ately sized for the system design according to national regional and local codes Electrical characteristics are within plus or minus 5 of rated values for Isc Voc Impp and Vmpp Modules may operate und...

Страница 9: ...um short circuit current of the system maximum operating temperatures and cable run lengths For field connections use at a minimum 12 AWG 4 mm2 wires insulated for a minimum of 85 C Use copper wire on...

Страница 10: ...erience and is believed to be accurate However all information in this manual without exception including recommendations and specifications does not constitute a warranty expressed or implied MEMC re...

Страница 11: ...ure C Maximum System Voltage V Limiting Reverse Current A Maximum Series Fuse Rating A 46 2 0 47 to 0 49 0 35 0 036 to 0 055 40 to 85 600 UL 1000 IEC 8 40 15 TEMPERATURE COEFFICIENTS AND PARAMETERS Mo...

Страница 12: ...46 2 0 49 0 35 0 055 40 to 85 600 UL 1000 IEC 8 40 15 TEMPERATURE COEFFICIENTS AND PARAMETERS Module Dimensions mm Module Weight kg Cell Type Number of Cells Frame Material Corner Caps Glass mm 1 674...

Страница 13: ...al 8 0 Appendix 8 1 Module dETAILS A 990 39 0 B 1 658 65 3 C 50 2 0 D 40 1 6 E 940 37 0 F 1 608 63 3 G 994 39 1 H 594 23 4 Module Dimensions Mounting Hole Spacing Dimension MM INCH Dimension MM INCH L...

Страница 14: ...PV Modules 14 of 15 Copyright 2012 MEMC Electronic Material Front View Bolt Stack Details Center Mount Option 8 0 Appendix 8 1A Module dETAILS M240 250 260LMA and M240 250 260LMC SPECIFIC dimensions...

Страница 15: ...tch printed version to documentation database MEMC Electronic Materials Inc 501 Pearl Drive City of O Fallon St Peters MO 63376 USA 1 636 474 5000 www sunedison com 8 0 AppendiX 8 3 Pre mounted Cables...

Отзывы: