3.2 STORAGE, UNPACKING, AND HANDLING

• 

Packaged modules must be stored in a dry and ventilated area.    

• 

Packaged modules must not be exposed to rain, snow, hail or other environmental conditions that may compromise the 
packaging material and the modules.  

• 

Packaged modules must be on appropriate provided pallets and must not be stacked more than two pallet high for storage. 

• 

Once the modules are opened, store modules in a dry and ventilated room.

• 

Modules should never be stored in a wet environment.

• 

Upon unpacking, do not carry a module by its wires or junction box. Only carry a module by its frame with two or more 
people. 

• 

Precaution should be taken to avoid damage to the glass surface with or without anti-reflective coating due to improper 
handling during storage or unpacking.

• 

Keep all electrical contacts clean and dry.

• 

All modules are manufactured with a sealed junction box and pre-attached cables and locking connectors. These 
components should not be modified or tampered with in any way.

• 

Do not allow unauthorized persons near the installation site or storage area of modules.

• 

Do not place modules on top of one another.

• 

Do not place any load on the module or twist the module frame.

• 

Do not stand, step, walk, or jump on the module.

• 

Do not drop or place objects on the modules such as tools.

• 

Do not handle modules with bare hands and avoid scratches, handling marks, or any damage especially to the front glass of 
the module, backsheet, or electrical components.

• 

Do not mark the modules with sharp instruments.

• 

Do not leave a module unsupported or unsecured. 

• 

Do not modify module frames in any way.

3.3 SAFETY

The following safety guidelines and best practices should be followed:

• 

All installations must be performed in compliance with all applicable regional and local electrical codes or other national or 
international electrical standards.

• 

Use insulated tools during installation, troubleshooting and maintenance of photovoltaic modules.

• 

Wear suitable protection to prevent direct contact with module’s electrical output and mechanical sharp edges.

• 

Cover the front of the modules with an opaque material to stop production of electricity when installing or working with a 
module or wiring.

• 

Modules connected in a series should not be disconnected under illumination. Disconnecting modules under illumination may 
cause electrical arcing which may result in burns, fires or other problems. 

• 

Follow industry best practices when commissioning, trouble shooting, disconnecting, or connecting a PV system.

• 

Trouble shooting should include planning, checking, disconnecting, cause seeking, replacement, and record keeping. 

• 

Do not install or handle the modules or their components when they are wet or during periods of high wind.

• 

Do not attempt to disassemble, repair, or open any part of the module including junction box or sub-components.

• 

Do not artificially concentrate sunlight on a module.

• 

Do not install or handle any broken modules. If a module is broken, or the back sheet is torn, contact with the surface or 
frame can cause an electrical shock.

Installation Manual: MEMC Silvantis P290 | M320

© Copyright 2012 MEMC Electronic Material

3 of 13

Содержание M305BCC

Страница 1: ...Installation Manual for MEMC SilvantisTM 72 cell Photovoltaic Modules Silvantis P290 Silvantis M320...

Страница 2: ...NG AND DESIGN 6 5 2 MODULE WIRING 6 5 3 GROUNDING 7 5 4 ELECTRICAL INSTALLATION WARNINGS 7 6 0 DISCLAIMER OF LIABILITY 8 7 0 MECHANICAL AND ELECTRICAL PARAMETERS AND SPECIFICATIONS 9 8 0 APPENDIX 11 8...

Страница 3: ...This may be required for product identification Damage to the glass surface or the anti reflective coating can impact the power output and overall efficiency of the system Scratches handling marks or...

Страница 4: ...ot mark the modules with sharp instruments Do not leave a module unsupported or unsecured Do not modify module frames in any way 3 3 SAFETY The following safety guidelines and best practices should be...

Страница 5: ...w referring to chart showing clamp and bolt mounting locations If using bolts four mounting holes are provided on the rear side the module frame as shown in Appendix 8 1 Use a stainless steel bolt sta...

Страница 6: ...2400 Pa or 50 psf Maximum Front Load 5400 Pa or 113 psf Maximum Rear Load 2400 Pa or 50 psf Maximum Front Load 2400 Pa or 50 psf CASE 1 Structural rails running perpendicular to the length of the modu...

Страница 7: ...000 V UL and 1000 V IEC Vocm equals the module open circuit voltage at coldest conditions for the site refer to local codes WARNING Installers should adhere to all applicable local regional and nation...

Страница 8: ...the star washer scratches the anodized frame 5 4 ELECTRICAL INSTALLATION WARNINGS Installation and maintenance should be performed by qualified personnel only Use insulated tools during installation...

Страница 9: ...cluding recommendations and specifications does not constitute a warranty expressed or implied MEMC reserves the right to change the manual the module or specifications without prior notice The produc...

Страница 10: ...oefficients may vary by 10 47 2 0 45 0 33 0 066 40 to 85 1000 UL IEC 8 40 15 0 5 IV CURVES AT MULTIPLE TEMPERATURES 1000 W m2 Current A Voltage V 10 5 0 0 2 4 6 8 10 15 20 25 30 35 40 45 50 15 C 25 C...

Страница 11: ...RACTERISTICS All electrical data at standard test conditions STC 1000W m2 AM1 5 25 C Electrical characteristics may vary by 5 and power by 0 5W Listed specifications are subject to change without prio...

Страница 12: ...GINEERING DRAWING SHOWN BELONGS TO THE FOLLOWING LISTED SILVANTIS MODULE SERIES P290 M320 A 990 39 0 B 1 976 77 8 C 50 2 0 D 30 1 2 E 22 0 9 Module Dimensions Dimension MM INCH F 950 37 4 G 1 188 46 8...

Страница 13: ...DIX 8 2 MODULE ILLUSTRATIONS Installation Manual MEMC Silvantis P290 M320 8 3 CLAMP DRAWINGS Copyright 2012 MEMC Electronic Material 12 of 13 A 6 35 0 3 B 38 1 5 Module Clip Dimensions Dimension MM IN...

Страница 14: ...00 V IEC 1000 V DC UL 1000 V Temperature rating 40 C to 90 C 40 C to 85 C Qualification TUV 2PFG UL PV wire EN 50521 UL for PV sys Copyright 2012 MEMC Electronic Material Controlled Document MEMC Elec...

Отзывы: