background image

NOTICE:

 Do not attempt to operate the SP device 

until the receptacle is mounted. The mounting bolts 

must be in place to maintain alignment of compo-

nents and compression against the panel or handle is 

required to maintain assembly.

SP series plugs and receptacles feature different 

mechanical keying of L1, L2, L3, N, and G.  Mating 

plug/receptacle combinations are color coded for 

easy identification.

SP series plugs and receptacles are not intended 

to be connected or disconnected under load. 

The pilot circuit must be used to control the 

 

  power circuit.

The pilot circuit can only be turned ‘on’ when the 

plug is engaged and the plug can only be removed 

when the pilot curcuit is in the ‘off’ position.      For 

safety, MELTRIC recommends the following connec-

tion sequence:  Ground, Neutral, Phase 1, Phase 2, 

Phase 3.

Connection

Insert the plug straight into the receptacle until a 

‘click’ is heard.  Figure  1  The plug and its flexible 

cable must not exert force on the receptacle.  

Pull on the plug to make sure it is properly latched 

in the receptacle.  Figure  2    A small rotation of the 

plug, in either direction, engages the locking finger on 

the receptacle to prevent any further rotation.   

To close the pilot circuit and mechanically lock the 

plug into the receptacle, turn the ring on the recep-

tacle until the “1” lines up with the arrow across from 

the release button.  Figure  3 

Do not attempt to turn the ring towards “1” 

when there is no plug engaged. Defeating the 

mechanical lock could create a potentially 

 

  hazardous condition if energized under load.

Disconnection

To open the pilot circuit and unlock the plug, turn the 

ring back until the “0” is aligned with the arrow. 

Figure  4   This action signals the controller to switch 

off the power and unlocks the plug.  To remove the 

plug, press firmly on the latch release button and 

simultaneously pull on the plug.  A slight rotation of 

the plug may be required before it can be removed.

Achieving rated watertightness

Rated IP66/67 watertightness to is achieved when 

the plug and receptacle are mated.  When discon-

nected, the receptacle cap must be fully inserted with 

the slot in the cap aligned with the protruding ‘button’.  

The plug cap must be pressed firmly into place.  

NOTICE:

 Proper steps must be taken to maintain 

watertightness at threaded connections on the plug    

handles or at the junction box.  The use of a sealer  

tape is recommended. 

 MAINTENANCE

WARNING: 

Before inspecting, repairing, or maintain-

ing MELTRIC products, disconnect electrical power to 

the receptacle to eliminate the risk of electrical shock.

 

MELTRIC products require little on-going mainte-

nance.  However, it is a good practice to periodically 

perform the following general inspections:

  

•  Check the mounting screws for tightness.

 

•  Verify that the weight of the cable is supported    

 

  by the strain relief mechanism and not by the 

 

  terminal connections.

 

•  Check the IP gaskets for wear and resiliency.     

 

  Replace as required.

 

•  Verify the electrical continuity of the ground  

 

   circuit.

 

•  Check the contact surfaces for cleanliness  

 

 

  and pitting.

Use a clean cloth to rub off deposits of dust or similar 

foreign materials on the contacts and the plug interiors.  

Sprays should not be used, as they tend to collect dirt.  

If any significant pitting of the contacts or other serious 

damage is observed, the device should be replaced.

 

MANUFACTURER’S RESPONSIBILITY

MELTRIC’s responsibility is strictly limited to the repair 

or replacement of any product that does not conform 

to the warranty specified in the purchase contract.  

MELTRIC shall not be liable for any penalties or 

consequential damages associated with the loss of 

production, work, profit, or any other kind of financial 

loss incurred by the customer.

MELTRIC Corporation shall not be held liable when 

its products are used in conjunction with products not 

bearing the 

 

technology trademark.  The use 

of MELTRIC products in conjunction with mating devic-

es that are not marked with the 

 

technology 

trademark shall void all warranties on the product.

MELTRIC Corporation

 is an ISO 9001 certified com-

pany.  Its products are designed, manufactured and 

rated in accordance with applicable UL, CSA and IEC 

standards.  MELTRIC designs and manufactures 

its products in accordance with Marechal keying 

standards established to ensure intermatablility with 

similarly rated products manufactured by Marechal 

Electric Group.

4

3

1

2

Latch

Release

Button

INSSP F