Installation manual
Outer wall terminals M-WRG-II ES (-P, -PK), M-WRG-II KSR (-1, -2)
- 14 -
Meltem Wärmerückgewinnung GmbH & Co. KG
Am Hartholz 4 · D-82239 Alling
[email protected] · www.meltem.com
VENTILATION THE RIGHT WAY
V E N T I L A T I O N & H E A T R E C O V E R Y
6.1
Installing the outer wall terminal stainless steel pod M-WRG-II ES (-P, -PK)
6.1.1
Checking the ventilation pipes
►
Check that the ventilation pipes
protrude 5 - 10 mm beyond the
external plaster (see item 1 in Fig. 7).
►
Check that the cut surfaces of the
ventilation pipes have been deburred
(see item 2 in Fig. 7).
NOTICE
The cut surfaces of the ventilation
pipes must be deburred. If this is not
the case, there is a risk that the seals
on the outer wall terminal base plate
will be damaged.
6.1.2
Drilling the holes for the outer wall
terminal
►
Press the pre-punched cut-outs
(item 1 in Fig. 8) for the ventilation
pipes out of the drilling template
(item 2 in Fig. 8).
►
Position the drilling template correctly
on the ventilation pipes and flush with
the facade.
NOTICE
— Note the “OBEN (TOP)” (item 3
in Fig. 8) printed on the drilling
template.
—
The fixing materials supplied are
intended for fixing the outer wall
terminal to brick walls.
►
Note the information on
facade structures.
► Use the 6 mm masonry bit to drill four holes, roughly 40 mm deep, in the external wall
at the points indicated on the drilling template (item 4 in Fig. 8).
►
Remove the drilling template.
►
Insert the four dowels provided (item 5 in Fig. 8) into the holes.
Fig. 7:
Checking the ventilation pipes
1
5 - 10 mm
2
Fig. 8:
Drilling the holes
1
2
3
4
5