- 24 -
Installation manual
M-WRG-II M
Meltem Wärmerückgewinnung GmbH & Co. KG
Am Hartholz 4 · D-82239 Alling
[email protected] · www.meltem.com
VENTILATION THE RIGHT WAY
V E N T I L A T I O N & H E A T R E C O V E R Y
Fig. 16 contains a typical plan for running the flexible pipes. Always run 2 flexible pipes in
the supply air or extract air room.
NOTICE
The dimensions of the channels for the
flexible pipes are:
— 170 mm wide
— 85 mm deep
NOTICE
► Observe the following recommendations when using flexible pipes to avoid unnec
-
essary pressure losses in the pipes.
—
Always connect two flexible pipes to the flexible pipe connection.
—
As far as possible, use flexible pipes with a diameter of 75 mm.
—
The total length of each flexible pipe should not exceed 10 m.
—
Minimise the number of bends in the flexible pipes.
—
Run the two flexible pipes of a flexible pipe connection in parallel to one another.
The minimum distance between the flexible pipes must not be less than 3x the
pipe diameter.
Fig. 16:
Planning example for running flexible pipes
(schematic representation)
min. 300
min. 3x
pipe di-
ameter