Getting Started: Pre-Installation Checklist 

Before connecting the Intelli-Hood system in your BACnet network, the system needs its 
network and BACnet specific configuration to be setup correctly.  If these settings are 
known prior to delivery, Melink can configure the Intelli-Hood system’s network and 
BACnet settings for you so it is ready when the system is installed.  Below is a quick 
checklist of settings that could be determined prior to installation.  Contact Melink prior 
to installation with the following configuration settings (either fill in by hand or copy 
details in some other manner) and these can be configured on your Intelli-Hood system 
prior to installation. 
 
Network Settings 
DHCP Enabled:  

Yes 

No 

Static IP: 

 

____________________ 

Netmask: 

 

____________________ 

DNS Server 1: 

____________________ 

DNS Server 2: 

____________________ 

 
System Controller BACnet Settings 
BACnet Device Instance ID:  

____________________ 

BACnet Auto Number: 

 

Yes 

No 

BACnet Port:  

 

 

____________________ 

BACnet DNET: 

 

 

____________________ 

 
Exhaust Fan 1 BACnet Settings 
BACnet Device Instance ID: 

____________________ 

BACnet Enabled:    

 

Yes 

No 

 
Exhaust Fan 2 BACnet Settings 
BACnet Device Instance ID: 

____________________ 

BACnet Enabled:    

 

Yes 

No 

 
Exhaust Fan 3 BACnet Settings 
BACnet Device Instance ID: 

____________________ 

BACnet Enabled:    

 

Yes 

No 

 
Exhaust Fan 4 BACnet Settings 
BACnet Device Instance ID: 

____________________ 

BACnet Enabled:    

 

Yes 

No 

 

 

 

Содержание Intelli-Hood IH3 SC

Страница 1: ...tegrity Innovation Service Excellence BACnet Protocol Implementation Conformance Statement PICS Version 7 0 Melink Document IH ENG DTS BAC 006 Melink Corporation 5140 River Valley Rd Cincinnati OH 451...

Страница 2: ...Drive 18 Networking Setup and Configuration 19 BACnet Setup and Configuration 20 Common BACnet Interfacing Use Cases 22 Monitoring Fan Speeds 22 Monitoring Energy Consumption 22 Setting Time on the In...

Страница 3: ...aust Fans and kitchen MUA Make Up Air units When smoke is created under normal cooking conditions the optic sensors signal the exhaust fan VFD to send the exhaust fan motor to full speed until all smo...

Страница 4: ...more information Analog Value Binary Value Device Data Link Layer Options BACnet IP Annex J Device Address Binding Is static device binding supported This is currently necessary for two way communicat...

Страница 5: ...ead only BV4 24VDC Out 1 Status Energized De Energized Read only BV5 24VDC Out 2 Status Energized De Energized Read only BV6 Analog Input Status 0 100 Read only AV0 Analog Output Status 0 100 Read onl...

Страница 6: ...s the list of possible digital input configurations and how they affect the Intelli Hood system Remote On Off A Remote On Off digital input is an edge sensitive input When the digital input changes st...

Страница 7: ...do not command fans to turn on or off but only set the minimum speed for the fans when they are on External Fault An External Fault digital input is a level sensitive input An External Fault input can...

Страница 8: ...guration and the state of the associated Hood Groups The following is a short description of each digital output configuration option and how the system state affects the digital output Temperature Al...

Страница 9: ...ted Hood Groups VFD Fault A VFD Fault digital output will be energized if there is any VFD Fault lost communication or VFD tripped due to a fault on any VFD in any associated Hood Group System Fault A...

Страница 10: ...ercent speed governed by this analog input whichever is highest Exhaust Fans are not affected Aux Add The analog input percentage is added to the calculated fan speed for the Auxiliary Airflows Exhaus...

Страница 11: ...lt has been resolved the VFD still will need its VFD fault cleared before the VFD will power a fan The Clear VFD Fault Binary Value can be used to attempt to clear a VFD Fault If the Clear VFD Fault B...

Страница 12: ...value Output Energy The reported kWh counter of the VFD The kWh counter is not available on all VFD models be sure it is available on your VFD if you would like to monitor this value Note that the In...

Страница 13: ...t Module Digital Input 1 through Digital Input 4 The Virtual Input Module has four digital inputs that mimic the operation of the physical digital inputs on the System Controller See the Digital Input...

Страница 14: ...list of the Objects available on the Virtual Input Module Digital Output 1 through Digital Output 4 The Virtual Output Module has four digital outputs that mimic the operation of the physical digital...

Страница 15: ...ese can be configured on your Intelli Hood system prior to installation Network Settings DHCP Enabled Yes No Static IP ____________________ Netmask ____________________ DNS Server 1 __________________...

Страница 16: ...ood Controller 2 BACnet Settings BACnet Device Instance ID ____________________ BACnet Enabled Yes No Hood Controller 3 BACnet Settings BACnet Device Instance ID ____________________ BACnet Enabled Ye...

Страница 17: ...at the same time and hold the buttons down for ten seconds System Configuration should change from red to blue to indicate that configuration is unlocked Release the Up and Down buttons at this point...

Страница 18: ...et to the Auxiliary Airflow s BACnet configuration settings 5 To get to the Hood Controller BACnet configuration settings from the Main Menu go to System Configuration Hood Controllers to get to the H...

Страница 19: ...the USB flash drive with the one titled ConfigurationFiles zip containing the latest configuration It is suggested that you keep a backup of the system configuration in a safe location in case you nee...

Страница 20: ...if the Intelli Hood system needs to communicate with devices on another network This is generally not needed unless you are setting up the system for remote access You can set this if DHCP is enabled...

Страница 21: ...evice Instance ID sequentially after the System Controller s Device Instance ID See Appendix A if you need specific details on how the automatic Device Instance Numbering works If you cannot use a seq...

Страница 22: ...Fan Auxiliary Airflow and Hood Controller Active on BACnet Given the number of Device Objects that are possible with the Intelli Hood system some sites may not need to monitor all devices and may want...

Страница 23: ...iary Airflow reports Fault Active on Binary Value 1 If there is a fault at the VFD or if the Intelli Hood system has lost communication to the VFD then Fault Active is set for that fan This may be use...

Страница 24: ...ystem s time from your Operator s Workstation The Intelli Hood system supports the UTC Time Synchronization service Follow your Operator Workstation s instructions on how to set a Device Object s time...

Страница 25: ...each virtual device when the System Controller auto assigns the Device Instance Numbers The System Controller Device Object is Device Instance Number defaults to 654000 Vendor ID x 1000 Each Exhaust F...

Страница 26: ...ll always be Binary Value 0 for each Exhaust Fan or Auxiliary Airflow Device Object MAC Address The MAC address for each Device Object is based upon the IP address of the Intelli Hood 3 System Control...

Страница 27: ...e Number Device Object MAC Address Device Object Name 654000 142 51 5 36 0xBAC0 System Controller 654001 36 5 51 1 0xBAC0 KEF 02 654002 36 5 51 2 0xBAC0 KEF 05 654003 36 5 51 3 0xBAC0 MUA 41 654004 36...

Страница 28: ...Hood Network Address 2 Hood Controller 3 HC 03 Hood Network Address 3 Hood Controller 4 HC 04 Hood Network Address 4 Resulting Device Object List Device Instance Number Device Object MAC Address Devic...

Страница 29: ...if you need to set the Device Instance Numbers to be within a certain range but do not care what the Device Instance Number is for a particular device The following is a modification to the previous e...

Страница 30: ...t Fans Auxiliary Airflows Hood Controllers Virtual Input Modules and Virtual Output Modules and auto numbers these devices When BACnet Auto Number is set to No the configured BACnet Device Instance Nu...

Страница 31: ...what you expected then check the configuration for that device Similarly you can find the assigned Device Instance Numbers for all Hood Controllers by navigating to Menu Status Hood Controllers The De...

Страница 32: ...uchpad or look at the label on the inside door of the System Controller enclosure If the serial number starts with V3 for example V300012 then you have a standard System Controller and BACnet communic...

Страница 33: ...BACnet networks Network Discovery or BACnet Discovery as described above If you discover a device that is setup with the Intelli Hood s DNET then determine whether to change the Intelli Hood s DNET o...

Страница 34: ...et Watchdog configuration settings The system will reset all the digital inputs and analog inputs on all Virtual Input Modules if the Intelli Hood system receives no BACnet communication for the time...

Страница 35: ...dated formatting to clarify device operation Removed references to BBMD and Foreign Device support 5 0 10 21 2015 Updated the Object Property Support Matrix to include the currently supported points A...

Отзывы: