Move DIP switch S1 located on the side of thermostat to ON position.

Adjust the temperature set point.
Above this temperature the outputs to the heaters will not be activated.

Adjust and enable/disable the low limit temperature.
When temperature on snow sensor drops below the low temperature limit, the 
heating system will stop.

Adjust and enable/disable the upper limit temperature, and display 
temperature on heaters sensor. 
Note: If the upper limit control is disabled, the heaters will work regardless of 
the upper limit.
Adjust the time delay before stopping the heaters. 
Note 1. The time delay countdown will start when the snow detection signal 
from snow sensor will switch from positive to negative. 
Note 2. The staggering sequence will continue during the time delay period.

Adjust  the “Manual ON” mode time period.
The delay time parameter defines a time frame in which the heaters remain 
ON after receiving a “Manual ON” command.

Adjust  the splitting time. The heaters cycle / splitting time parameter defines 
the full cycle working time of all the heaters when working in sequence.

Adjust the snow sensor sensitivity value
(20% - Less sensitive, 80% - more sensitive)

Select the number of PYROSENSE snow sensors connected.

Turn ON test conditions to check the functionality of the system regardless of 
sensors parameters. Use some water to wet the circuit on top of the snow 
sensor. Note: If the technician did not manually exit test/commissioning mode, 
the unit will automatically return to normal mode after 5 hours.

Move DIP switch S1 located on the side of thermostat to OFF position.

Enable/Disable 

1 – Enable

0 - Disable

Adjust 

+41…+86°F

+5…+30°C

Def: +30°C/+86°F

Enable/Disable

1 – Enable

0 - Disable

Display 

temperature

on heaters

Adjust hours

00…99

Def: 00

Adjust minutes

00…59

Def: 30

Adjust minutes

10…1999

Def: 24

Select

0...3

Def. 0

Adjust 

20...80%

Def: 50%

Select 

1,2,3 or 4

Def: 1

Adjust

Adjust 

-4…+23°F

-20…-5C°C

Def: -20°C/-5°F

Enable/Disable

P01

Temperature

set point

P02

Low limit

temperature

P03

Upper limit 

temperature

P04

Time delay

P05

Manual ON

P06

Splitting time

P07

Logic of sensors

And outputs

P08

Snow sensor 

sensitivity

P09

Number of 

snow sensors

P10

Test mode

(commissioning)

Save changes 

and Exit

technician 

settings

Enter 

technician 

settings

Adjust hours

00…99

Def: 6

Adjust minutes

00…59

Def: 00

T. (856) 2882882 | T. +972-3-9626462 | F. +972-3-9626620

support@meitavtec

.

com | www.meitavtec.com

Restore default values
Important: Make sure the unit is turned OFF (the word 

“OFF” should appear on display).

Move DIP switch S1 to ON position.

Press and hold the [ON] button for 10 seconds. 

Move DIP switch S1 back to OFF position.
DIP switch S2 - Short measuring times (test only)

- “ON” - Short measuring times – for test/commissioning only 

(measuring times will be divided to 60).

- “OFF” - Normal operation.

Short measuring times: A real 1 hour will take 1 minute and a 

real 1 minute will take 1 second. 
DIP switches S3 and S4 – heaters sequencing logic

Use DIP switches S3 and S4 to define the sequencing logic of 

the heater (zones) as follows:

All 4 outputs work per request from the snow sensor(s)

Outputs 1+3 and outputs 2+4 work together (by splitting time)
Note: Do not use this configuration with more than two snow 
sensors connected.  

Outputs 1,2 and 3 work in sequence (by splitting time) and 
output 4 works continuously.
Note: Do not use this configuration with more than two snow 
sensors connected.  

All 4 outputs work in sequence (by splitting time)
Note: Do not use this configuration with more than two snow 
sensors connected.  

Note: if output 5 is set to work together with outputs 1-4, (see 

“Heater output no. 5 logic” in the technician settings), it will 

operate the same as output 4.

Enable/Disable zones
Turn Unit OFF.
While OFF, press both the [+] and [-] buttons for 10 sec.
Press the [Select] button to select zone.
Press the [+] and [-] buttons enable/disable the selected zone.
Black - Enabled zone. White – Disable zone.
Press both the [+] and [-] buttons for 5 seconds to exit.

“0” - 1-5 by PYROSENSE. 4 & 5 operate together.
“1” - 1-4 by PYROSENSE. 5 by 3

rd

 party.

“2” - 1-5 by 3

rd

 party. Temperature display blank.

“3” - 1-3 by PYROSENSE. 4 & 5 by 3

rd

 party.

Define heaters control by 
PYROSENSE sensor 
or by 3

rd

 party sensor.

PYROCON12 | Fast Ref

erence Guide

P88

Snow sensor 

threshold

Adjust minutes

00…60

Def: 5

Adjust the threshold.
If the threshold is not reached, the logic of turning the heaters either ON or 
OFF will not be affected by snow detection.
During countdown to threshold time, the snow flake icon will flash.

Rev

5.2.4

Important: Changes made to technician parameters will not take effect 
as long as DIP switch S1 is in ON position.

Содержание PYROCON12

Страница 1: ...PYROCON12 Controller and User Interface panel Owner s manual Technician Settings ...

Страница 2: ...d splitting time 9 P07 Heater outputs logic by PYROSENSE or by 3rd party sensor 10 P08 Snow sensor sensitivity 10 P88 Snow detection threshold 10 P09 Number of snow sensors connected 11 P10 Test conditions mode 11 Save changes end return to normal display 11 Restore default values 11 DIP Switch settings 12 DIP switch S2 Short measuring times test only 12 DIP switches S3 and S4 heaters sequencing l...

Страница 3: ...ble temperature scales F or C Adjustable Lower ambient temperature limit to stop Both Automatic and Manual modes heaters lockout Adjustable heaters cycle and splitting times Energy saving temperature limit Adjustable heaters hold on off delay Adjustable snow sensor sensitivity Optional auxiliary control based 3rd party Commissioning Test environment snow sensor e g Gutter sensor Tel 856 2882882 Te...

Страница 4: ...OSENSE 4 optional PYROSENSE 3 optional PYROSENSE 2 optional PYROSENSE 1 last in comm Line 4 2 1 Supply PYROULS Upper limit Sensor 10K 25 C 1 2 3 GIT 1 Aux Gutter ice sensor optional Black Red White PYROCON12 R R C C R C Z1 Z2 Z3 Z4 A B 3 To contactors 5 EGFPD C R C B A Blue Red Black White R C B A Blue Red Black White R C B A Blue Red Black White R C B A Blue Red Black White JBOX JBOX JBOX JBOX Co...

Страница 5: ...d shielded twisted pair 120 Ohm 18AWG Up to 500ft 150m Important When connecting more than one sensor snow sensor 1 must be connected last in communication line Shield Shield Notes The number of snow sensors connected must be configured in section P09 of the technician settings When one of the snow sensors cannot be viewed through communication faulty or not connected the values on snow sensor 1 w...

Страница 6: ...ing temperature scale Press the button for Celsius Press the button for Fahrenheit Tel 856 2882882 Tel 972 3 9626462 Fax 972 3 9626620 support meitavtec com PYROCON12 Owner s manual Technician Settings Pg 6 Heaters indication Heater ON Heater OFF The number beneath the heater icon indicates the heater stage 1 to 5 Stg 1 Stg 2 Stg 3 Stg 4 Stg 5 Black icon Heater ON White icon Heater OFF A solid sno...

Страница 7: ...per slab temperature limit to stop heaters P04 Time delay before stopping the heaters P05 ON time for manual mode P06 Heaters cycle time Splitting time P07 Sensors and heaters control logic P08 Snow sensor sensitivity P88 Snow detection threshold P09 Number of snow sensors connected P10 Commissioning Test mode Restore defaults Move DIP switch S1 located on the side of thermostat to ON position Pre...

Страница 8: ...rdless of the upper limit Press the SELECT and buttons simultaneously again The display will show the temperature on the upper limit sensor Upper limit temperature Set point enabled P03 disabled P02 Lower limit temperature for heating Press the SELECT and buttons simultaneously P02 and the low limit temperature will appear on display When the temperature on the temperature sensor drops below the l...

Страница 9: ...inutes will blink The heaters cycle splitting time parameter defines the working time of the heaters when working in sequence Example the splitting time is set to 10 minutes and 4 heaters work in sequence each heater will be ON for 2 5 minutes 10 4 2 5 Use the and buttons to adjust the splitting time Range 10 1999 minutes Default 24 minutes Splitting time Cont P04 Time delay before stopping the he...

Страница 10: ... by snow detection During countdown to threshold time the snow flake icon will flash Snow detection threshold Technician settings Cont P07 Heaters outputs logic controlled by PYROSENSE snow melt sensor or by 3rd party sensor Note 3rd party sensors i e gutter or pavement sensors CIT GIT SIT by eti Outputs controlled by PYROSENSE Outputs controlled by 3rd party sensor 0 All outputs 1 1 2 3 4 5 2 All...

Страница 11: ...sioning mode the word Test will disappear from display Note If the technician did not manually exit test commissioning mode the unit will automatically return to normal mode after 5 hours In order to save changes and return to normal display move DIP switch S1 back to OFF position Test conditions mode Restore default values Important Make sure the unit is turned OFF the word OFF should appear on d...

Страница 12: ...f the heater zones as follows S3 OFF S4 OFF All 4 outputs work per request from the snow sensor s S3 OFF S4 ON Outputs 1 3 and outputs 2 4 work together according to splitting time Note Do not use this configuration with more than two snow sensors connected S3 ON S4 OFF Outputs 1 2 and 3 work in sequence according to splitting time and output 4 works continuously Note Do not use this configuration...

Страница 13: ...ne black heater icon 5 Use the button to disable the selected zone white heater icon 6 Repeat steps above 3 to 5 for any required zone 7 Press and hold both the and the buttons simultaneously again for 5 seconds to return to normal display Note Disabled zones will be ignored in splitting time calculations Example the splitting time is set to 60 minutes and heaters are set work in sequence 3 Heater...

Страница 14: ...ions 1 Refer to P03 section of the technician settings 2 Check the temperature value and disable the sensor if needed 3 Replace the sensor The system will continue to operate using constant predefined values In addition the display will alternate between LO and 11 F 24 C for low temperature readings and between HI and 55 F 13 C for high temperature readings Communication error with snow sensors Er...

Страница 15: ...Notes Tel 856 2882882 Tel 972 3 9626462 Fax 972 3 9626620 support meitavtec com PYROCON12 Owner s manual Technician Settings ...

Страница 16: ...Tel 856 2882882 Tel 972 3 9626462 Fax 972 3 9626620 support meitavtec com www meitavtec com ...

Страница 17: ...ve changes and Exit technician settings Enter technician settings Adjust hours 00 99 Def 6 Adjust minutes 00 59 Def 00 T 856 2882882 T 972 3 9626462 F 972 3 9626620 support meitavtec com www meitavtec com Restore default values Important Make sure the unit is turned OFF the word OFF should appear on display Move DIP switch S1 to ON position Press and hold the ON button for 10 seconds Move DIP swit...

Отзывы: