Technician settings (Cont’)
P03 -Time delay before stopping the heaters
Tel: (856) 2882882
Tel: +972-3-9626462
Fax: +972-3-9626620
support@meitavtec.com
PYROBOX3/3C/5
-TRACE
Owner’s manual & Technician Settings
Pg. 10
Press the [SELECT] and [+] buttons simultaneously.
“P03”, “dL” and the time delay before stopping the heaters (Hold ON) will
appear on display. The hours will blink.
Use the [+] and [-] buttons to adjust the hours of the time delay.
Range: 0000...9999 minutes
Default: 120 minutes
Note 1. The time delay countdown will start when the ambient temperatures
rises above the set point temperature.
Note 2. The staggering sequence will continue during the time delay period.
Time delay
(minutes)
Cont’
P02 - Lower limit temperature for heating
Press the [SELECT] and [+] buttons simultaneously.
“P02” and the low limit temperature will appear on display.
When the temperature on the temperature sensor drops below the low
temperature limit, the heating system will stop.
Use the [+] and [-] buttons to adjust the temperature set point.
Range: -40…+23°F / -40…-5°C
Default: -40°F / -40°C
Press the [SELECT] and [+] buttons simultaneously again.
The word “ON” or “OFF” will appear on display.
Use the [+] and [-] buttons enable (ON) or disable (OFF) the P02
parameter.
If disabled, the heating system will operate without low temperature
limitations.
Low limit
Temperature
P02
enabled
P02
disabled