4. Technician settings (cont’)
- 33 -
P85 – Deice in cool – cut-in temperature (AC only!)
Range: -20...99°C
Default: 0°C
P86 – Deice in cool – cut-out temperature (AC only!)
Range: -20...99°C
Default: 8°C
P87 – Deice in heat time (AC only!)
Range: 120...420 Seconds
Default: 300 Seconds
P88 – Deice in heat break time (AC only!)
Range: 600...1800 Seconds
Default: 1500 Seconds
P89 – Deice in heat – cut-in temperature (AC only!)
Range: -20...99°C
Default: 0°C
P90 – Deice in heat – cut-out temperature (AC only!)
Range: -20...99°C
Default: 16°C
P91 – Compressor delay (AC only!)
Range: 0...360 Seconds
Default: 10 Seconds