4. Technician settings (cont’)
- 26 -
P49 – Shift between Cool and Heat in Auto change over mode
Range: 0...10°C / 0…20°F
Default: 2°C / 4°F
P51 – Shift between Heating stages
Range: 0...10°C / 0…20°F
Default: 2°C / 4°F
P52 – Cool proportional band (FC only!)
Range: 2...10°C / 4…20°F
Default: 2°C / 4°F
P53 – Cool proportional low limit (FC only!)
Range: 0...100%
Default: 0%
P54 – Cool proportional high limit (FC only!)
Range: 0...100%
Default: 100%
Содержание MTS/SUPER
Страница 1: ...Touch Screen Wall Panel MTS SUPER Owner s manual and technician settings...
Страница 2: ...2...
Страница 10: ...1 2 5 6 3 4 10 2 Installation Instructions cont...
Страница 34: ...34 Comments...
Страница 35: ...Comments 35...