DIP Switch and Jumpers Configuration
Internal/External Sensor
1
2
3
4
5
6
Internal
sensor
External
sensor
HC
HP
ON
OFF
X
X
X
X
S
w
itc
h
Heat Pump in
heat “B”
Heat Pump in
cool “O”
X
X
X
X
Time delay for compressor
3 Minutes
No delay
ON*
OFF
Oil/Gas
heat
Electric
heat
OFF*
ON
ON
OFF*
X
X
X
X
X
X
X
X
X
X
ON
OFF*
X
X
X
X
X
X
X
X
X
X
X
X
X
X
OFF*
ON
ON*
OFF
*Default
The DIP Dwitch is located on the top of the back side of the thermostat (above the connectors).
ON
1 2 3 4 5 6
Default DIP switch position:
External sensor Connection (option)
Important: The external sensor must be Meitav-tec type only!
Temp °C
7.2
10.0
12.8
15.6
18.3
21.1
23.9
26.7
29.4
32.2
Res. KΩ
115.8
100.9
88.1
77.1
67.7
59.6
52.5
46.4
41.2
36.6
Connecting the external sensor
Disconnect power to the thermostat.
Move switch 5 to ON position and switches 1 and 6 to OFF position.
Connect the temperature sensor to the T-T terminals.
Reconnect power to the thermostat.
Notes:
The wire length for the external sensor can be up to 100 feet (30 meters) with standard cable.
If the distance is greater than 30 meters (100 feet) the wire MUST be shielded.
There is a wide range of sensors for different applications, duct, rooms, etc. There are also options for
averaging the temperature. For details please contact our technical line or visit our web site.
ON
1 2 3 4 5 6
For
complete reset of the unit
, use
JMP1
(3 pins) as follows: move the jumper from “A”
position to “B” position, wait 30 seconds and move the jumper back to “A” position.
JMP2
(2 pins) is
not in use
and must always stay shorted.