DIP Switch and Jumpers Configuration

Internal/External Sensor

1

2

3

4

5

6

Internal

sensor

External

sensor

HC

HP

ON

OFF

X

X

X

X

S

w

itc

h

Heat Pump in 

heat “B”

Heat Pump in 

cool “O”

X

X

X

X

Time delay for compressor

3 Minutes

No delay

ON*

OFF

Oil/Gas

heat

Electric

heat

OFF*

ON

ON

OFF*

X

X

X

X

X

X

X

X

X

X

ON

OFF*

X

X

X

X

X

X

X

X

X

X

X

X

X

X

OFF*

ON

ON*

OFF

*Default

The DIP Dwitch is located on the top of the back side of the thermostat (above the connectors).

ON

1 2 3 4 5 6

Default DIP switch  position:

External sensor Connection (option)

Important: The external sensor must be Meitav-tec type only!

Temp °C

7.2

10.0

12.8

15.6

18.3

21.1

23.9

26.7

29.4

32.2

Res. KΩ

115.8

100.9

88.1

77.1

67.7

59.6

52.5

46.4

41.2

36.6

Connecting the external sensor

Disconnect power to the thermostat.

Move switch 5 to ON position and switches 1 and 6 to OFF position.

Connect the temperature sensor to the T-T terminals.

Reconnect power to the thermostat.

Notes:

The wire length for the external sensor can be up to 100 feet (30 meters) with standard cable.

If the distance is greater than 30 meters (100 feet) the wire MUST be shielded. 

There is a wide range of sensors for different applications, duct, rooms, etc.  There are also options for 

averaging the temperature. For details please contact our technical line or visit our web site.

ON

1 2 3 4 5 6

For 

complete reset of the unit

, use 

JMP1 

(3 pins) as follows: move the jumper from “A” 

position to “B” position, wait 30 seconds and move the jumper back to “A” position.

JMP2 

(2 pins) is 

not in use

 and must always stay shorted.

A

B

JMP2

JMP2

JMP1

Tel: +972-3-9626462
Fax: +972-3-9626620
www.meitavtec.com | [email protected]

ETN24-SUPER-PROG-US-C-LOCK-7DAYS

Owner’s manual & Technician Settings