6. Technician Settings 

 

6.1 

 

Set differential for 0÷10Vdc.  

  The temperature Differential defines the ratio 

between the opening level of the damper and the 

temperature demand. The damper will be fully 

opened when the demand (demand = ambient temp 

– set temp) equals the differential. 

(Differential range: 2°C÷10°C) 

  Press and hold the MODE button – a number will 

appear on the display. 

  Adjust the differential using the “+” or “-” buttons. 

 

(In the picture – the differential was 2°C and changed to 6°C) 

 

6.2  Proportional output selection 0÷10Vdc or 2÷10Vdc 

 

 

 

Press the MODE button again - “0” and “SET” will 

appear on display. 

  Using the “+” button, change the scale to 2÷10Vdc 

“2” will appear on display. 

  Using the “-” button, change the scale to 0÷10Vdc 

“0” will appear on display. 

  Press the MODE button again to return to normal 

display mode. 

 

(In the picture – the scale was 2÷10Vdc and changed to 0÷10Vdc) 

 

6.3 

 

Set Offset for temperature reading.  

The Offset is used for field calibration of the 

measured temperature if necessary.   

(Offset range -6°C÷6°C) 

  Press the MODE button again – a number will 

appear on the display. 

  Change the Offset for ambient temperature using 

the “+” or “-” buttons. 

  Press the MODE button again or wait to return to 

normal display mode. 

 

(In the picture – the offset was 0°C and changed to -2°C) 

 

Note: If no key is pressed for 5 seconds, the thermostat will automatically 

return to normal display mode. 