6
Operation
6.1 Setting the switch
point
Setting the switch point of an
installed device
The following instructions
describe the procedure for a
Normally Open Contact (NOC).
The actual state (open or
closed), can be determined
using a continuity meter.
Personnel:
n
Qualified personnel
Tools:
n
Flat-bladed screwdriver
1.
Adjust the flow to be monitored
and read it off at the scale on
the device. The top edge of the
float is the read-off point
Fig. 33: Loosen set screws
2.
Loosen the set screws of the
switch contact (Fig. 33/1) using
a flat-bladed screwdriver
3.
Slowly push the switch contact
in the opposite direction of flow
up to the stop
Operation
Setting the switch point
03.09.2018
DWG Module BASICS Flow Monitor
47