6 M300 - Rear connectors

6.4 PZF Antenna

Cable:

shielded coaxial line

Cable Length:

max. 300m to RG58

Connector:

BNC female

Center frequency:

77,5kHz

Signal level:

50

µ

V - 5 mV

Supply voltage:

3.5 V - 5 V

Impedance:

50 Ohm

PZF Antenna

WARNING!

Working on the antenna system during thunderstorms

Danger to life due to electrical shock!

- Do not carry out any work on the antenna system or the antenna cable

if there is a risk of a lightning strike.

- Do not carry out any work on the antenna system if the safety distance

to free lines and sequential circuits is exceeded.

LANTIME M300 PZF

Date: 3rd September 2019

21

Содержание LANTIME M300 PZF

Страница 1: ...TECHNICAL REFERENCE LANTIME M300 PZF NTP Time Server with PZF Receiver 3rd September 2019 Meinberg Radio Clocks GmbH Co KG...

Страница 2: ......

Страница 3: ...2 10 Return of Electrical and Electronic Equipment 12 3 Global Information LANTIME M300 PZF 13 4 Technical Specifications LANTIME Chassis 14 5 LANTIME M300 Front connectors 16 6 M300 Rear connectors 1...

Страница 4: ...Funkuhren GmbH Co KG Lange Wand 9 31812 Bad Pyrmont Germany Phone 49 0 52 81 93 09 0 Fax 49 0 52 81 93 09 230 Internet https www meinbergglobal com Mail info meinberg de Date 2019 09 03 LANTIME M300 P...

Страница 5: ...only continue if you have understood and fulfilled all requirements In this documentation dangers and indications are classified and illustrated as follows DANGER The signal word indicates an imminent...

Страница 6: ...ines elektrischen Schlages Caution risk of electric shock IEC 60417 5041 Vorsicht hei e Oberfl che Caution hot surface IEC 60417 6056 Vorsicht Gef hrlich sich bewegende Teile Caution moving fan blades...

Страница 7: ...ed for the purpose described in this manual In particular the given limits of the device must be observed The safety of the installation in which the unit is integrated is the responsibility of the in...

Страница 8: ...Installation in an air conditioned control cabinet required Transport Unpacking Installation If the unit is brought into the operating room from a cold environment condensation may occur wait until t...

Страница 9: ...operly and are undamaged Pay particular attention to the facts that the cables do not have kinks or that they are not too short around corners and no objects are placed on the cables Also make sure th...

Страница 10: ...e mains socket on the appliance or the mains socket of the house installation is freely accessible to the user so that the mains cable can be pulled out of the socket in case of emergency Outside the...

Страница 11: ...onductor via the protective earth connection terminal If an external earth connection is provided on the housing it must be connected to the equipotential bonding rail grounding rail The mounting part...

Страница 12: ...led and when the doors are closed cooling fire protection shielding against electrical magnetic and electromagnetic fields Switch off in fault service case By switching off the devices are not disconn...

Страница 13: ...for the user and result in a loss of warranty as well as an exclusion of liability Danger due to moving parts keep away from moving parts Device parts can become very hot during operation Do not touc...

Страница 14: ...ction Prepare removal and installation of assemblies Unload yourself for example by touching a grounded object before touching assemblies Ensure that you wear a grounding strap on the wrist when worki...

Страница 15: ...product symbol on the left indicates that this electronic product must not be disposed of in domestic waste Return and Collection Systems For returning your old equipment please use the country specif...

Страница 16: ...nal reference as well as a combination of these references hybrid system External references are also possible The LANTIME system is a set of equipment composed of an integrated PZF receiver a single...

Страница 17: ...al sheet steel Temperature range Operation 0 50 C 0 122 F Storage 20 70 C 4 158 F Relative humidity Operation max 85 non condensing at 30 C Maximum altitude Operation max 2000 m 6562 ft above sea leve...

Страница 18: ...mm 17 51 inch 304 mm 11 98 inch 288 mm 11 32 inch External Ground Connection on the Housing This connector must be wired to an equipotential bonding bar earthing bar Connection is possible on both si...

Страница 19: ...f the display the op erating mode of the reference clock reference time is shown Instead of PZF NORMAL OPERATION the messages PZF NO SIGNAL can appear In case the antenna connection is interrupted the...

Страница 20: ...it is possible to configure the parameters with a terminal program To establish a connection between the LANTIME and a PC use a NULL MODEM cable Configure your terminal pro gram with 38400 Baud 8 Data...

Страница 21: ...W Heat Emission Etherm 108 00 kJ h 102 37 BTU h O I 100 240 V 50 60 Hz WARNING This equipment is operated at a hazardous voltage Danger to life due to electrical shock Only qualified personnel electri...

Страница 22: ...al Baudrate framing 19200 8N1 default Timestring Meinberg Standard default Assignment Pin 2 TxD transmit Pin 3 RxD receive Pin 5 GND ground Connection type D SUB female 9pin Cable data cable shielded...

Страница 23: ...AC 60 VA Switching Current UL CSA 0 46 A 140 V AC 0 46 A 65 V DC 1A 30 V DC Response Time ca 2ms Normal Operation Mode Normal Operation CO NO connected CO NO NC Error Mode Error CO NC connected CO NO...

Страница 24: ...ance 50 Ohm PZF Antenna WARNING Working on the antenna system during thunderstorms Danger to life due to electrical shock Do not carry out any work on the antenna system or the antenna cable if there...

Страница 25: ...cy Output Output signal 10MHz frequency Signal level TTL 2 5 V into 50 Ohm Connector BNC female Cable shielded coax line 10MHz Out 6 7 10 100Base T Network Port IEEE 803 2 Output signal 100Base T Data...

Страница 26: ...or attenuate the reception For this reason we always recommend to mount the antenna outside of buildings This has the advantage that the signal interference distance to electronic devices in buildings...

Страница 27: ...noise in the associated frequency range For standard longwave receivers it is important that the modulation mark is blinking exactly once per second without intermediate flickering DCF77 PZF receiver...

Страница 28: ...rcury hexavalent chromium polybrominated biphenyls PBBs and polybrominated diphenyl ethers PBDEs above the legal threshold WEEE status of the product This product is handled as a B2B Business to Busi...

Страница 29: ...en bereinstimmt to which this declaration relates is in conformity with the following standards and provisions of the directives RED Richtlinie ETSI EN 303 413 V1 1 1 2017 06 RED Directive 2014 53 EU...

Отзывы: