4 ESI - Telecom Synchronisation References
Input 2:
The input 2 accepts as input either 2048/1544 kHz frequency or configurable frequency in range be-
tween 1 kHz and 20 MHz, also 1.544kHz if required.
Type:
Frequency input
Frequency:
1 kHz - 20 MHz of input signal, 10 MHz is set as default.
Maximum Slip:
A discontinuity of an integer number of cycles in the measured carrier phase resulting from
a remporary loss of input signal. The maximum slip number can be selected in range between
0.5 – 3 cycles, with 1.5 as a default value.
Input 3:
See Input 2, but with RJ45 Connector and as default Frequency input 2048 kHz.